Stp - Number Of First Step Assigned To Program - gefran 850 Installation And Instruction Manual

Double pid temperature controller
Table of Contents

Advertisement

4.7.1.
PR.OP.N - Selecting program
Acronym
PR.OP.N
PROGRAM NUMBER
The parameter lets you select the program to be configured. During normal functioning, the controller shows the number
of the program running and its state P.STAT, viewable in the User Configuration menu.
Unit of measurement:
Options:
1...16
4.7.2.
FI.STP - Number of first step assigned to program
Acronym
FI.STP
PR.OPT.1 (o PR.OPT.2... PR.OPT.16) FIRST STEP OF PROGRAM
The parameter lets you select the first step of the program.
This parameter is visible only if "Simplified Programmer" is deactivated (S.PROG parameter set to OFF)
Unit of measurement:
Options:
1...192
4.7.3.
LA.STP - Number of last step assigned to program
Acronym
LA.STP
PR.OPT.1 (o PR.OPT.2... PR.OPT.16) LAST STEP OF PROGRAM
The parameter lets you select the last step of the program.
This parameter is visible only if "Simplified Programmer" is deactivated (S.PROG parameter set to OFF)
ATTENTION: LA.STP cannot be less than FI.STP.
Unit of measurement:
Options:
FI.STP...192
4.7.4.
STRT - Restart mode
Acronym
Strt
PR.OPT.1 (o PR.OPT.2... PR.OPT.16) RESTART TYPE AFTER POWER-ON
The parameter defines program restart mode after Power-on.
Unit of measurement:
Options:
FI.STP = Program restarts from first step, with setpoint attributed or equal to PV based on the
ST.STP = Program restarts from condition in which it stopped (last step in execution, setpoint
RSRCH = Program restarts with search for step (see programmer function...).
4.7.5.
RST.SP - Type of control after program restart
Acronym
RST.SP
PR.OPT.1 (or PR.OPT.2... PR.OPT.16) CONTROL TYPE AFTER RESET
The parameter defines the type of control that the controller runs after a reset while waiting for restart.
With RST.SP = On the setpoint takes the value of PV with reset command active.
Unit of measurement:
Options:
OFF
On
Scrolling message
Number
Scrolling message
Number
Scrolling message
Number
Scrolling message
-
following parameter RST.SP
Scrolling message
-
= The controller continues the control, maintaining the active setpoint
= The setpoint assumes the value of the process variable (PV) by imposing the control
output to zero.
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 73
Submenu
Attributes
PR.OPT
R W
Submenu
Attributes
PR.OPT
R W
Submenu
Attributes
PR.OPT
R W
Submenu
Attributes
PR.OPT
R W
Submenu
Attributes
PR.OPT
R W

Advertisement

Table of Contents
loading

This manual is also suitable for:

16501850

Table of Contents