in the case of a valve model with auxiliary input, linear custom type FUnC=VALV.P function, and with
VALV.P = Auxiliary input calibration with valve position function.
if model has custom auxiliary input 2:
I.AUX2 = Calibration of custom auxiliary input 2 (selected with TYPE parameter in INPUT.3 menu).
* is the case of C.RTD, linearisation with 32 broken LIN=32STP must be enabled
4.31.2. FI.CAL - Resetting the factory calibration
Acronym
FI.CAL
FACTORY CALIBRATION
The parameter shows and sets resetting of the factory calibration.
This operation can be done only for inputs and outputs, if U.CAL corresponds to I.MAIN, I.AUX, I.CT1, I.CT2, OUT.A1,
OUT.A2 or OUT.C.
Unit of measurement:
Options:
no
YES

4.31.3. C.LOW - Calibrating minimum current / voltage

Acronym
C.LOW
The parameter appears if you are calibrating a main input or custom auxiliary input in current or voltage.
To calibrate:
apply the current or voltage value corresponding to minimum scale value to the selected input;
press the
key to acquire the calibration value.
Unit of measurement:
Options:
-

4.31.4. C.HIGH - Calibrating maximum current / voltage

Acronym
C.HIGH
The parameter appears if you are calibrating a main input or custom auxiliary input in current or voltage.
To calibrate:
apply the current or voltage value corresponding to maximum scale value to the selected input;
press the
key to acquire the calibration value.
Unit of measurement:
Options:
-
one output set as V.OPEN and one output set as V.CLOS input configuration:
It is made up of 6 progressive phases:
Phase 1: START CALIBRATION message, switch to phase 2 after approximately 4 sec.
Phase 2: VALVE OPEN message and indication of increasing percent progress, output
V.OPEN is on for the time set in parameter TRAVL in sub-menu VALVE increased by 10%
and switch to phase 3.
Phase 3: SAVE MAX message, the maximum auxiliary input calibration value is saved
and switch to phase 4.
Phase 4: VALVE CLOSE message and indication of decreasing percent progress, output
V.CLOS is on for the time set in parameter TRAVL in sub-menu
VALVE increased by 10% and switch to phase 5.
Phase 5: SAVE MIN message, the minimum auxiliary input calibration value is saved and
switch to phase 6.
Phase 6: END CALIBRATION message, calibration ends after approximately 4 sec.
Calibration only occurs for the valve model with auxiliary input, linear custom type
FUnC=VALV.P function, and with an output set as V.OPEN and output set as V.CLOS.
Calibration can be aborted at any time by pressing the regulator key
Scrolling message
-
= Keep user calibration
= Reset factory calibration
Scrolling message
-
Scrolling message
-