4.18.12. FAULT - State of output with broken input

Acronym
FAULT
OUTPU.1 (o OUTPU.2 ... OUTPU.4) FAULT OUTPUT STATE
The parameter shows and sets the state (ON, OFF) that the output assumes in case of sensor fault (Err, Sbr, ...), on main
input IN.1 or auxiliary input IN.2, if the output is direct or inverse and automatic operation mode.
Unit of measurement:
Options:
OFF.1
On.1
nOnE
if the model with auxiliary input:
OFF.2
On.2
OF.12
On.12

4.18.13. MSG.OU - Selecting the output message

Acronym
MSG.OU
OUTPU.1 (o OUTPU.2 ... OUTPU.4) NUMBER OF SCROLLING MESSAGE AT
OUTPUT ACT
The parameter shows and sets the number of the message assigned to activation of the output, i.e., the scrolling messa-
ge shown on the display.
For more information on scrolling messages, see paragraph "3.1.2.2. Scrolling messages" on page <?>.
If the parameter is set to "0" no message will be displayed when the output is activated.
The same message number can be assigned to different outputs.
Unit of measurement:
Options:
0...25 (with LAnG=LANG1 or LANG2 or LANG3)
0...75 (with LAnG=NONE)
4.18.14. LO.C – Low limit for continuous output / HI.C
Acronym
LO.C
LOW LIMIT CONTINUE OUTPUT
This parameter shows and sets the low limits of the scale, corresponding to the minimum output voltage or current.
Every time the F.ou.C parameter of power control output is set, the value of this parameter is forced to 0.
This parameter only applies if Output 1 is of the CONT.A or CONT.C type.
Unit of measurement:
Options:
-1999...9999
4.18.15. HI.C – Massimo di scala per uscita continua
Acronym
HI.C
HIGH LIMIT CONTINUE OUTPUT
This parameter shows and sets the high limits of the scale, corresponding to the maximum output voltage or current.
Every time the F.ou.C parameter of power control output is set, the value of this parameter is forced to 1000.
This parameter only applies if Output 1 is of the CONT.A or CONT.C type.
Unit of measurement:
Options:
-1999...9999
Scrolling message
-
= Output OFF in case of fault on main input IN.1
= Output ON in case of fault on main input IN.1
= Output continues to function normally
= Output OFF in case of fault on auxiliary input IN.2
= Output ON in case of fault on auxiliary input IN.2
= Output OFF in case of fault on input IN.1 or IN.2
= Output ON in case of fault on input IN.1 or IN.2
Scrolling message
Message number
Scrolling message
Points on the scale of quantities associated with continuous output
Scrolling message
Points on the scale of quantities associated with continuous output
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 138
Submenu
Attributes
OUTPU
R W
Submenu
Attributes
OUTPU
R W
Submenu
Attributes
OUTPU
R W
Submenu
Attributes
OUTPU
R W