4.18.5. TYPE - Defining the type of continuous output

Acronym
TYPE
CONTINUE OUTPUT TYPE
The parameter shows and sets the definition of continuous output.
The parameter applies only to Output 1 of CONT.A
Unit of measurement:
Options:
20MA
4-20M
10V
2-10V
C.20MA = 0...20 mA custom output
C.4-20 = 4...20 mA custom output
C.10V
C.2-10 = 2...10 V custom output

4.18.6. F.OU.C - Selecting the function assigned to continuous output

Acronym
F.ou.C
REFERENCE SIGNAL CONTINUE OUTPUT
The parameter shows and sets the function assigned to continuous output 1, direct or inverse.
The parameter applies only to Output 1 of CONT.A. or CONT.C.
Unit of measurement:
Options:
NONE
HEAT1 = Heat control output of PID.1
COOL1 = Cool control output of PID.1
PV1
SSP1
SETP1 = Local setpoint of PID.1
DEVI1
SERIA
H+C1
if PID2.E function is enabled in EN.FUN in EN.FUNC e parametro FUNC=PV2 in INPUT.2:
HEAT2 = PID.2 heat control output
COOL2 = UPID.2 control output
H+C2
PV2
SSP2
SETP2 = PID.2 local setpoint
DEVI2
IN1
if the model with auxiliary input:
IN2
if the model with auxiliary input 2:
IN3
Scrolling message
-
= 0...20 mA output
= 4...20 mA output
= 0...10 V output
= 2...10 V output
= 0...10 V custom output
Scrolling message
-
= No assigned function
= Process variable 1
= Active setpoint of PID.1
= Deviation |SSp-PV| of PID.1
= Value set from serial line
= PID.1 heat/cool control output
= PID.2 heat/cool control output
= Process variable 2
= PID.2 active setpoint
= PID.2 deviation |SSp-PV|
= Main input
= Auxiliary input
= Auxiliary input 2