GENERAL DATA
Operating voltage
Power dissipation
POWER SUPPLY
Protections
Connection
Serial configuration port
RS485
(option)
Master Modbus
CONNECTIONS
RTU Bridge
Ethernet Modbus TCP e
Webserver
(opzione)
Inputs and outputs
Use
Altitude
AMBIENT
Operating temperature
CONDITIONS
Storage temperature
Relative humidity
PROTECTION LEVEL
Positioning
Installation regulations
ASSEMBLY
DIMENSIONS
WEIGHT
EMC conformity
(electromagnetic compatibility)
CE STANDARDS
LVD safety
CERTIFICATIONS
1) Programming is done with the GF_eXpress configuration program.
Generals
Europe
USA, Canada
Russia
80209C_MHW_850-1650-1850_01-2020_ITA_pag. 272
100...240 VAC/VDC ±10%, 50/60 Hz
(20...27 VAC/VDC ±10%, 50/60 Hz)
10 W max
Overvoltage 300 V / 35 V
Screw terminals and crimp connector, max. wire section 1 mm
Connector: microUSB
Baudrate: 1200, 2400, 4800, 9600, 19.200, 38.400, 57.600,
115.200 bit/s
Protocol: Modbus RTU
Insulation compared to main entrance
Screw terminals and crimp connector, max. wire section 2.5mm
Baudrate: 1200, 2400, 4800, 9600, 19.200, 38.400, 57.600,
115.200 bit/s
Protocol: Modbus RTU Master
Connector: RJ10
Baudrate: 1200, 2400, 4800, 9600, 19.200, 38.400, 57.600,
115.200 bit/s
Protocol: Modbus RTU Master
Screw terminals and crimp connector, max. wire section 2.5mm
Baudrate : 10/100BaseTX, 10/100Mbit/s
Protocol : Modbus TCP slave, integrated Webserver
Isolamento compared to other peripherals
RJ45 Standard connector
Screw terminals and crimp connector, max. wire section 2.5mm
Indoor
2000 m max
-10 ... +55 °C (as per IEC 68-2-14)
-20 ... +70 °C (as per IEC 68-2-14)
20...85% RH non-condensing (as per IEC 68-2-3)
IP 65 on front panel (as per IEC 68-2-3)
On panel, removable faceplate
Installation category: II
Pollution degree: 2
Isolation: double
48 X 96 mm (1/8 DIN)
Depth: 80 mm
0,24 kg
Conforms to Directive 2014/30/EU norme EN 61326-1
Emissions in industrial environment classe A
Conforms to Directive 2014/35/EU norme EN 61010-1
This Gefran controller, when subjected to the necessary cal-
ibration operations in the field, is suitable for use in Nadcap
applications for any class of oven, from 1 to 6, according to
specification AMS2750E, paragraph 3.3.1.
CE, RoHS, REACH
UL, cUL
EAC
2
2
2
2