gefran 850 Installation And Instruction Manual page 269

Double pid temperature controller
Table of Contents

Advertisement

GENERAL DATA
Operating voltage
POWER SUPPLY
Power dissipation
Protections
Connection
Serial configuration port
RS485
(option)
CONNECTIONS
AMBIENT
CONDITIONS
Inputs and outputs
Use
Altitude
PROTECTION LEVEL
Operating temperature
Storage temperature
ASSEMBLY
Relative humidity
DIMENSIONS
WEIGHT
Positioning
Installation regulations
CE STANDARDS
PESO
EMC conformity
NORME CE
(electromagnetic compatibility)
LVD safety
CERTIFICATIONS
1) Programming is done through the GF_eXpress configuration program
Master Modbus
RTU Bridge
Ethernet Modbus TCP
and Webserver (optional)
Generals
Europe
USA, Canada
Russia
80209C_MHW_850-1650-1850_01-2020_ITA_pag. 267
100...240 VAC/VDC ±10%, 50/60 Hz
(20...27 VAC/VDC ±10%, 50/60 Hz)
10 W max
Overvoltage 300 V / 35 V
Screw terminals and crimp connector, max. wire section 1 mm
Connector: microUSB
Baudrate: 1200, 2400, 4800, 9600, 19.200, 38.400, 57.600, 115.200
bit/s
Protocol: Modbus RTU slave
Insulation respect to main input
Screw terminals and crimp connector, max. wire section 2,5mm
Baudrate: 1200, 2400, 4800, 9600, 19.200, 38.400, 57.600,
115.200 bit/s
Protocol: Modbus RTU Master
Screw terminals and crimp connector, max. wire section 2,5mm
Baudrate: 1200, 2400, 4800, 9600, 19.200, 38.400, 57.600,
115.200 bit/s
Protocol: Modbus RTU Master
Screw terminals and crimp connector, max. wire section 2,5mm
Baudrate : 10/100BaseTX, 10/100Mbit/s
Protocol : Modbus TCP slave, Webserver integrato
Isolation from other peripherals
Standard RJ45 conector
Screw terminals and crimp connector, max. wire section 2,5 mm
Internal
2000 m max
-10 ... +55 °C (as per IEC 68-2-14)
-20 ... +70 °C (as per IEC 68-2-14)
20...85% RH non-condensing (as per IEC 68-2-3)
IP 65 on front panel (as per IEC 68-2-3)
On panel, removable faceplate
Installation category: II
Pollution degree: 2
Isolation: double
48 X 48 mm (1/16 DIN),
Depth: 100 mm
0,16 kg
Conforms to Directive 2014/30/EU norme EN 61326-1
Emissions in industrial environment classe A
Conforms to Directive 2014/35/EU norme EN 61010-1
This Gefran controller, when subjected to the necessary cal-
ibration operations in the field, is suitable for use in Nadcap
applications for any class of oven, from 1 to 6, according to
specification AMS2750E, paragraph 3.3.1.
CE, RoHS, REACH
UL, cUL
EAC
2
2
2
2
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

16501850

Table of Contents