4.31.5. RTD.LO - Calibrating minimum resistance value
Acronym
RTD.LO
The parameter appears if you are calibrating a main input or custom RTD auxiliary input.
To calibrate:
•
apply a resistance corresponding to minimum scale value to the main input (for example, 18.52 Ω for Pt100) ;
•
press the
key to acquire the calibration value.
Unit of measurement:
Options:
-
4.31.6. RTD.HI - Calibrating maximum resistance value
Acronym
RTD.HI
The parameter appears if you are calibrating a main input or custom RTD auxiliary input.
To calibrate:
•
apply a resistance corresponding to maximum scale value to the main input (for example, 390.48 Ω for Pt100);
•
press the
key to acquire the calibration value.
Unit of measurement:
Options:
-
4.31.7. HOUR - Setting hours
Acronym
HOUR
The parameter shows and sets the hours on the Real Time Clock, if U.CAL = RTC.
Unit of measurement:
Options:
0...23
4.31.8. MIN - Setting minutes
Acronym
MIN
The parameter shows and sets the minutes on the Real Time Clock, if U.CAL = RTC.
Unit of measurement:
Options:
0...59
4.31.9. SEC - Setting seconds
Acronym
SEC
The parameter shows and sets the seconds on the Real Time Clock, if U.CAL = RTC.
Unit of measurement:
Options:
0...59