Advertisement

4.18.4. F.OUT - Selecting the function assigned to relay, logic or Triac output

Acronym
F.out
OUTPU.1 (o OUTPU.2... OUTPU.4) OUTPUT FUNCTION
The parameter shows and sets the function assigned to the output with identifying number "x", if the output is relay, logic
or Triac and is direct or inverse.
Unit of measurement:
Options:
NONE
HEAT1 = Heat control output of PID.1
COOL1 = Cool control output of PID.1
ALRM1 = Output for Alarm 1
ALRM2 = Output for Alarm 2
ALRM3 = Output for Alarm 3
ALRM4 = Output for Alarm 4
OR.12
OR.123 = Alarm 1 OR Alarm 2 OR Alarm 3
O.1234 = Alarm 1 OR Alarm 2 OR Alarm 3 OR Alarm 4
AND.12 = Alarm 1 AND Alarm 2
AN.123 = Alarm 1 AND Alarm 2 AND Alarm 3
A.1234 = Alarm 1 AND Alarm 2 AND Alarm 3 AND Alarm 4
if model with CT1+CT2:
AL.HB
LBA1
BUT.SR = Set/Reset from key
if the Timer function is enabled in MODE.1:
TIMR1 = Timer state (end of count)
if the Programmer 1 function is enabled in parameter PROGR on the EN.FUN menu:
P.HBB1 = HBB alarm of programmer of PROGR.1
P.RUN1 = RUN state of programmer of PROGR.1
P.HLD1 = STOP state of programmer of PROGR.1
P.RDY1 = READY state of programmer (after reset of time base) of PROGR.1
P.END1 = END state of programmer ofPROGR.1
P.EVE1 = EVENTO state of programmer of PROGR.1
if model with Logic Operations:
LFB.O
if model with valve control:
V.OPEN = Output for the opening of the valve
V.CLOS = Output for the closure of the valve
if model with digital inputs:
IN.DIG = Repetition of a digital input
POWR1 = Output for PID.1 power alarm
if PID2.E function is enabled in EN.FUN:
HEAT2 = PID.2 heat control output
COOL2 = PID.2 cool control output
LBA2
POWR2 = Output for PID.2 power alarm
if the Timer function is enabled in MODE.2:
TIMR2 = TIMER.2 timer state (end count)
if the Programmer 2 function is enabled in parameter PROGR on the EN.FUN menu:
P.HBB2 = HBB programmer PROGR.2 alarm
P.RUN2 = RUN programmer PROGR.2 state
P.HLD2 = STOP programmer PROGR.2 state
P.RDY2 = READY programmer PROGR.2 state (after reset of time base)
P.END2 = END programmer PROGR.2 state
P.EVE2 = EVENTO programmer PROGR.2 state
if model with Master Modbus serial (except output 1) and at least one Master parameter configured
as MASTER:
MASTER = Master value (for type provided to word only) (index no. to be specified in MAST.N)
Scrolling message
-
= No assigned function
= Alarm 1 OR Alarm 2
= Output for HB alarm
= Output for LBA alarm of PID.1
= Output of Function Blocks
= PID.2 LBA alarm output
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 135