4.14.25. FEEDF - Feedforward power
Acronym
FEEDF
PID.1 (o PID.2) FEEDFORWARD
The parameter shows and sets the feedforward power value, i.e., the value that generates an additional factor at the
control output based on the setpoint value.
Unit of measurement:
Options:
-100.0...100.0
4.14.26. DEAD.B - Deadband
Acronym
DEAD.B
PID.1 (or PID.2) DEAD BAND
The parameter shows and sets the deadband.
The deadband is symmetrical to the setpoint. If the process value (PV) stays in this band, the control output keeps the
required power value constant.
Unit of measurement:
Options:
0...999
4.14.27. FAULT - Fault action power
Acronym
FAULT
PID.1 (or PID.2) FAULT ACTION POWER
The parameter shows and sets the fault action power, supplied if the sensor is broken.
Example
If Cntr = HP.CON (Proportional Heat, ON/OFF Cool), the option is On, OFF, 0.0...100.0, i.e., if you set FAULT = On the
cooling output will be ON in case of fault.
Unit of measurement:
Options:
-100.0...100.0
On, OFF
4.14.28. GRAD.I - Setpoint gradient in increase
Acronym
GRAD.I
PID.1 (or PID.2) SETPOINT GRADIENT IN INCREMENT
The parameter shows and sets the gradient used when the setpoint value is increased.
If the parameter is "0.0" the gradient is disabled.
Unit of measurement:
Options:
0.0...999.9
Scrolling message
setpoint
U =
end of scale - start of
scale
%
Scrolling message
Scale points of main or auxiliary input.
Scrolling message
%
for P or PI or PID action
for ON / OFF action
Scrolling message
digit/second or digit/minute, depending on unit parameter setting
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 120
FEEDF
X
100.0
Submenu
Attributes
PID
R W
Submenu
Attributes
PID
R W
Submenu
Attributes
PID
R W
Submenu
Attributes
PID
R W