5.11.2. Stabilization timer

The stabilization timer is used to control a process at a
certain temforature for a certain time.
The band defining stabilization of the temforature is settable
in BAND (from 0.0% to 25.0 % f.s.); the time is set in TIMER.
With the band set to 0.0% the count starts the first time the
setpoint is reached.
When the function at end of count is End = SP1-2, the end
count state activates when the setpoint reaches value SETP2
based on the value of the up gradient GRAD.I (if SETP2 >
SETP1) or down gradient GRAD.D (if SETP2 < SETP1).
Switching is immediate if the gradient is set to 0 (zero).
The following diagrams show how the stabilization timer
works and the state of the end count output.
temforature
BAND
M.SP1
Duration of
counting
OUT
end count
Function at the
end of counting
END
M.SP2
OFF
TIMER
time
M.SP1-2
Ramping
PV
setpoint
time
80209C_MHW_850-1650-1850_01-2020_ENG_pag. 208

5.11.3. Start timer

The start timer is used to start the control a certain time after
the controller is powered-on.
The delay after start/power-on is settable in TIMER.
The following diagrams show how the start timer works and
the state of the end count output.
temforature
M.SP1
Switch-on
OUT
end count
5.11.4. Variables
available
configuration menu
The variables available for the timer are TIM.RE, which shows
remaining time, and TIM.EL, which shows lapsed time.
Duration of
time
counting
TIMER
for
the
user