4.31.1. U.CAL - Selecting the user calibration

Acronym
U.CAL
USER CALIBRATION TYPE
The parameter shows and sets the parameter, input or output to which calibration will be applied.
Unit of measurement:
Options:
NONE
if model with CT1+CT2:
AL.HB
.
RTC
if energy counting mode is enabled in MODE.1:
ENRG1 = Reset energy count 1 (totalizer EN.KWH1 and time EN.TIM1)
P.DAYS = Reset partial day count
if the main input is custom:
I.MAIN = Calibration of custom main input (selected with parameter TYPE on INPUT.1 menu)*
if the model with auxiliary input is custom:
I.AUX
if model with CT1+CT2:
I.CT1
I.CT2
if the model with analogue output OUT.A1 is custom:
OUT.A1 = Calibration of custom retransmission output (selected with parameter t.o.A1 on OUT.AN menu)
if the model with analogue output OUT.A2 is custom:
OUT.A2 = Calibration of custom retransmission output (selected with parameter t.o.A2 on OUT.AN menu)
if the model with continuous output (OUT.A for 850 - OUT.C for 1650-1850) is custom:
OUT.C
if energy counting mode is enabled in MODE.2:
ENRG2 = Reset energy count 2 (E.KWH2 totalizer and E.TIM2 time)
CY.RES = Reset switching cycle count shown in INDG.S
Scrolling message
-
= No calibration
= HB alarm calibration. It is made up of 3 progressive phases:
Phase 1: OUTPUT SWITCH ON message, the output is 100% on when button F is pressed
(set in the OUT parameter in sub-menu AL.HB) and the transition to phase 2 takes place.
Phase
2:
CALIBRATION
(set in parameter THR.PE in sub-menu AL.HB) is calculated and saved in the LOW.
ON parameter when button F is pressed (F), and the transition to phase 3 takes place.
Phase 3: END CALIBRATION message, calibration ends when button F is pressed.
= Real Time Clock setting
if the model has no buffer battery, the data in the RTC at each power-on are initialized to:
HOUR = 0
MIN = 0
dAY = MONDA
DATE = 1
YEAR = 00
= Calibration of custom auxiliar input (selected with parameter TYPE on INPUT.2 menu)*
= CT1 input custom calibration
= CT2 input custom calibration
= Calibration of custom continuous output
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 188
RUNNING
message,
the
SEC = 0
Mont = JANUA
Submenu
Attributes
US.CAL
R W
percent
current
value