4.14.15. COOL - Selecting cooling fluid
Acronym
COOL
PID.1 (or PID.2) COOLING MEDIA
The parameter shows and sets the fluid used for cooling.
The parameter appears if the parameter Cntr = PID.RGn was selected.
Unit of measurement:
Options:
FAN
OIL
H2O
4.14.16. C.SP - Cooling setpoint with respect to heating setpoint
Acronym
C.SP
PID.1 (or PID.2) COOLING SETPOINT RELEVANT TO HEATING SETP
The parameter shows and sets the cooling setpoint as a percentage change of the heating setpoint.
Negative values superimpose cooling on heating.
Unit of measurement:
Options:
-25.0...25.0
4.14.17. C.PB - Proportional cooling band or hysteresis in ON-OFF control
Acronym
C.PB
PID.1 (or PID.2) COOLING PROPORTIONAL BAND OR ON/OFF HYST
The parameter shows and sets the proportional cooling band or hysteresis in the ON-OFF control, calculated as a per-
centage of full scale of the main or auxiliary input.
Unit of measurement:
Options:
0.0...999.9
4.14.18. C.IT - Integral cooling time
Acronym
C.IT
PID.1 (or PID.2) COOLING INTEGRAL TIME
The parameter shows and sets the integral cooling time.
Unit of measurement:
Options:
0.00...99.99
4.14.19. C.DT - Derivative cooling time
Acronym
C.DT
PID.1 (or PID.2) COOLING DERIVATIVE TIME
The parameter shows and sets the derivative cooling time.
Unit of measurement:
Options:
0.00...99.99
Scrolling message
-
= Air (relative gain H.PB/C.PB = 1)
= Oil (relative gain H.PB/C.PB = 0,8)
= Water (relative gain H.PB/C.PB = 0,4)
Scrolling message
%, of full scale of main or auxiliary input
Scrolling message
%
Scrolling message
Minutes
Scrolling message
Minutes