4.22.5. LO.RE - Defining transition from remote SP to local SP
Acronym
LO.rE
MODE.1 (o MODE.2) REMOTE TO LOCAL TRANSITION TYPE
The parameter shows and sets controller behavior when switching from remote to local setpoint, and is significant only
with Func = SETP or RATIO.
With STAND, the setpoint switches to the value of the selected local SP or multiset, possibly with setpoint gradient (if set).
With BUMPL, the remote SP value is memorized in the selected local SP or multiset.
Unit of measurement:
Options:
STAND
BUMPL
4.22.6. MA.P.L - Enabling manual power latch
Acronym
MA.P.L
MODE.1 (o MODE.2) MANUAL POWER LATCH ENABLE
The parameter shows and sets enabling of memorization (in non-volatile memory) of the manual power value.
Unit of measurement:
Options:
LATCH = Latch enabled
NO.LAT = Latch disabled. After Power-on, Manual power value is reset
4.22.7. MAN.P - Enabling change of manual power value
Acronym
MAn.P
MODE.1 (o MODE.2) MANUAL POWER MODIFY ENABLE
The parameter shows and sets enabling of change of the manual power value.
Unit of measurement:
Options:
MODIF
NO.MOD = Change not allowed
4.22.8. TMER - Enabling Timer function
Acronym
tMEr
MODE.1 (o MODE.2) TIMER ENABLE
The parameter shows and sets enabling of the Timer function.
The Timer function is explained in detail in paragraph "5.11. Timer" on page <?>.
Unit of measurement:
Options:
OFF
ON.SEC = Timer enabled with time base Seconds
ON.MIN = enabled with time base Minutes
Scrolling message
-
Scrolling message
-
Scrolling message
-
= Change allowed
Scrolling message
-
= Timer disabled
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 153