4.11.8. LATCH - Memorizing the alarm

Acronym
LATCH
ALARM.1 (or ALARM.2...ALARM.4) MEMORY DEFINITION
The parameter shows and sets enabling of memorization of the alarm being configured.
Memorization maintains the active alarm state even after the alarm conditions are eliminated.
The alarm state can be deleted by from the digital input, serial input, or key.
Unit of measurement:
Options:
OFF
On

4.11.9. HYSTE - Hysteresis

Acronym
HYSTE
ALARM.1 (or ALARM.2...ALARM.4) HYSTERESIS
The parameter shows and sets the hysteresis applied to the alarm setpoint value for the alarm being configured.
Unit of measurement:
Options:
0...999
-999...999

4.11.10. DELAY - Alarm trip delay

Acronym
DELAY
ALARM.1 (or ALARM.2...ALARM.4) DELAY OF ACTIVATION
The parameter shows and sets the alarm trip delay for the alarm being configured, i.e., the time that the value of the process
variable has to exceed the alarm setpoint for the alarm to trip.
This parameter prevents repeated alarms due to instantaneous and insignificant exceeding of that value.
If the parameter is set to "0.00" the alarm will be instantaneous, regardless of the time in which the process variable exce-
eds the alarm setpoint.
For a detailed explanation of this behavior, see paragraph "5.6.1. AL1...AL4 Generic alarms" on page <?>.
Unit of measurement:
Options:
0.00...99.59

4.11.11. MSG.AL - Message associated with tripping of alarm

Acronym
MSG.AL
ALARM.1 (or ALARM.2...ALARM.4) SCROLLING MESSAGE AT ALARM ACT
The parameter shows and sets the number of the message associated with tripping of the alarm being configured, i.e.,
the scrolling message shown on the display.
For more information on scrolling messages, see paragraph "3.1.2.2. Scrolling messages" on page <?>.
If the parameter is set to "0" no message will be displayed when the alarm trips.
The same message number can be assigned to different alarms
Unit of measurement:
Options:
0...25 (with LAnG=LANG1 or LANG2 or LANG3)
0...75 (with LAnG=NONE)
Scrolling message
-
= Alarm not latched
= Alarm latched
Scrolling message
Scale points
= For absolute (A.r.x = ABSLT) and symmetrical alarm (n.S.x = SYMMT)
= For other types of alarms
Scrolling message
Minutes.seconds
Scrolling message
Message number
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 103
Submenu
Attributes
ALARM
R W
Submenu
Attributes
ALARM
R W
Submenu
Attributes
ALARM
R W
Submenu
Attributes
ALARM
R W

Advertisement

Table of Contents
loading

This manual is also suitable for:

16501850

Table of Contents