4.4.1.
SW.VER - Versione software
Acronym
SW.VER
SOFTWARE VERSION
The parameter shows the version (major.minor) of the controller software.
Unit of measurement: -
Options:
4.4.2.
CODE - Identifying code of controller
Acronym
CODE
INSTRUMENT ID CODE FOR SERIAL COMM
The parameter shows identifying code of the device for serial communication.
Unit of measurement:
Options:
4.4.3.
ERROR - Main input error
Acronym
ERROR
MAIN INPUT ERROR
The parameter shows error detected by the main input.
Unit of measurement:
Options:
4.4.4.
SAP.C - SAP code
Acronym
SAP.C
SAP ORDER CODE
The parameter shows the product number (Fxxxxxx).
Unit of measurement:
Options:
4.4.5.
SEr.n - Serial number of controller
Acronym
SEr.n
SERIAL NUMBER
The parameter shows the serial number of the controller (number shown on data plate).
The serial number is displayed in the form yy.ww nnnn, where
yy
= last two digits of year of production
ww
= week of production
nnnn
= progressive in week of production
Unit of measurement:
Options:
40524-04 Rev0
Gefran 650/1250/1350 Temperature Controller – Abbreviated Manual
Scrolling message
-
Scrolling message
-
0...247
Scrolling message
-
nonE
= No error
Lou
= Process variable (PV) is below lower scale limit
HIGH
= Process variable (PV) is higher than upper scale limit
Err
= PT100 in short circuit or input values below lower limit
(for example, TC with incorrect connection)
Sbr
= Sensor break or input values higher than upper limit
Scrolling message
-
-
Scrolling message
-
-
4. CONFIGURATION
Password
Description
INFO
R
Password
Description
INFO
R
Password
Description
INFO
R
Password
Description
INFO
R
Password
Description
INFO
R
47