4.7.1.

tyPE - Selecting sensor type

Acronym
tyPE
MAIN INPUT TYPE OF PROBE
The parameter shows and sets the sensor type of the main input.
The functions for calibrating Custom sensors are on the US.CAL menu.
When a 4...20 mA input is used and the current is less than 2 mA, an Err message is generated and the relay state speci-
fied with the FAUL.T parameters is activated.
The table shows the scale limits for each sensor type or input based on the set number of decimals.
Sensor type
Thermocouple
Infrared
characteristic
of the
Tc K model
see note
Resistance
thermometer
Voltage /Current
Custom
Nota: the infrared temperature sensor has an output in voltage for direct connection to the input terminals of the temperature con-
troller. An external thermometer is needed in order to correct the sensor error.
After identifying the work temperature range (for example, 140 – 260°C), set an SP near the minimum scale value, and after rea-
ching it make a note of value A1 indicated by the instrument and of value A2 indicated by the external thermometer. Set an SP near
the maximum scale value, and after reaching it make a note of value B1 indicated by the instrument and of value B2 indicated by
the external thermometer. Enable 4-point linearization (see Correcting 4-point input) and enter the four requested values (A1, B1
.
and A2, B2).
64
40524-04 Rev0
Gefran 650/1250/1350 Temperature Controller – Abbreviated Manual
Scrolling message
Unit of
Scale limits for
Sensor
measure-
ment
J
°C
K
°C
R
°C
S
°C
T
°C
C
°C
D
°C
Pt20Rh
°C
Pt40Rh
1
°C
2
°C
3
°C
4
°C
PT100
°C
PT100
°C
JPT100
°C
0...60 mV
0...20 mA
4...20 mA
0...10 V
2...10 V
-1999...9999
0...5 V
1...5 V
0...1 V
0.2...1 V
RTD
0...60 mV
0...20 mA
4...20 mA
0...10 V
-1999...9999
2...10 V
0...5 V
1...5 V
0...1 V
0.2...1 V
Scale limits for
DEC.P = 0
DEC.P = 1
0...1000
0.0...999.9
0...1300
0.0...999.9
0...1750
0.0...999.9
0...1750
0.0...999.9
-200...400
-199.9...400.0
0...2300
0.0...999.9
0...2300
0.0...999.9
0...1880
0.0...999.9
10...70
10.0...70.0
60...120
60.0...120.0
115...165
115.0...165.0
140...260
140.0...260.0
-200...850
-199.9...850.0
-50...100
-50.0...100.0
-200...600
-199.9...850.0
-199.9...999.9
-199.9...999.9
Submenu
Attributes
I.MAIN
Error @ 25°C
< 1.6°C
with scale 0...1750 °C: < 2°C
(T > 100 °C)
< 1.6°C
< 1.6°C
< 1.6°C
< 5.1°C (T>1000°C)
maximum error 0.5°C
maximum error 0.5°C
maximum error 0.5°C
maximum error 0.5°C
< 1°C
< 1°C