2. Safety Instructions and General Warning

2.1.1. Disposal Instructions
FC 300
This Instruction Manual can be used for all FC 300 adjustable frequency drives with software
version 4.5x.
The software version number can be found in parameter 15-43.
Equipment containing electrical components may not be disposed of
together with domestic waste.
It must be collected separately as electrical and electronic waste in
accordance with local and currently valid legislation.
The FC 300 AutomationDrive DC link capacitors remain charged after power has
been disconnected. To avoid electrical shock, disconnect the FC 300 from the line
supply before carrying out maintenance procedures. When using a PM motor, make
sure it is disconnected. Before servicing the adjustable frequency drive, wait the
minimum amount of time indicated below:
380-500 V
0.33-10
[0.25-7.5 kW]
15-100 hp [11-75
kW]
125-300
[90-200 kW]
350-550
[250-400 kW]
525-690 V
50-350
[37-250 kW]
450-750
[315-560 kW]
Instruction Manual
Software version: 4.5x
MG.33.A9.22 - VLT is a registered Danfoss trademark
2. Safety Instructions and General Warning
hp
4 minutes
15 minutes
hp
20 minutes
hp
40 minutes
hp
20 minutes
hp
30 minutes
FC 300
2
7