Parameters
6-16 Terminal 53 Filter Time Constant
Range:
0.01 s
[0.01 - 10
*
3
3
s]
6-19 Terminal 53 mode
Option:
[0] Current mode
[1] Voltage mode

3.7.3 6-2* Analog Input 54

Parameters for configuring the scaling and limits for
analog input 54 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
0.07 V
[0 - 10
*
V]
6-21 Terminal 54 High Voltage
Range:
10 V
[0 - 10 V] Enter the voltage (V) that corresponds to the
*
6-22 Terminal 54 Low Current
Range:
4 mA
[0 - 20
*
mA]
6-23 Terminal 54 High Current
Range:
20 mA
[0 - 20 mA]
*
20.00 mA
[par. 6-22-20.00
*
mA]
3-32
VLT
Function:
Enter the time constant. This is a first-order
digital low pass filter time constant for
suppressing electrical noise in terminal 53. A
high time constant value improves
dampening but also increases the time
delay through the filter.
This parameter cannot be adjusted while
the motor is running.
Function:
Select if terminal 54 is used for current or
voltage input.
Function:
Enter the voltage (V) that corresponds to the
low reference value (set in 6-24 Terminal 54
Low Ref./Feedb. Value). The value must be set
at >1 V in order to activate 6-01 Live Zero
Timeout Function.
Function:
high reference value (set in 6-25 Terminal 54
High Ref./Feedb. Value).
Function:
Enter the low current value. This reference
signal should correspond to the low
reference/feedback value, set in 6-24 Terminal
54 Low Ref./Feedb. Value. The value must be
set at >2 mA in order to activate the Live
Zero Timeout Function in 6-01 Live Zero
Timeout Function.
Function:
Enter the high current value
corresponding to the high
MG18B222 - VLT
®
HVAC Basic Drive Programming Guide
6-23 Terminal 54 High Current
Range:
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
0
[-4999 - 4999 ] Enter the reference or feedback value that
*
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Size related
*
6-26 Terminal 54 Filter Time Constant
Range:
0.01 s
[0.01 - 10
*
s]
6-29 Terminal 54 mode
Option:
[0] Current mode
[1] Voltage mode

3.7.4 6-7* Analog/Digital Output 45

Parameters for configuring the scaling and limits for
analog/digital output Terminal 45. Analog outputs are
current outputs: 0/4-20 mA. Resolution on analog output is
12 bit. Analog output terminals can also be set up for
digital output.
6-70 Terminal 45 Mode
Option:
[0] 0-20 mA
[1] 4-20 mA
[2] Digital Output
®
is a registered Danfoss trademark
Function:
reference/feedback value set in
6-25 Terminal 54 High Ref./Feedb.
Value.
Function:
corresponds to the voltage or current set in
6-21 Terminal 54 High Voltage/6-22 Terminal
54 Low Current.
Function:
[-4999 - 4999 ]
Function:
Enter the time constant. This is a first-order
digital low pass filter time constant for
suppressing electrical noise in terminal 54. A
high time constant value improves
dampening but also increases the time
delay through the filter.
This parameter cannot be adjusted while
the motor is running.
Function:
Select if terminal 54 is used for current or
voltage input.
Function:
Set terminal 45 to act as analog output or as
digital output.