OPERATING THE AT30

2.3.3. Setting the Equalize Timer

• Press the
MANUAL TIMER and AUTO EQLZ TIMER indicators all light. The
display will flash the present value (hours) of the equalize timer duration.
Press and release the
the display by one count. Press and hold the keys to scroll the values
upward or downward. If a desired value is passed, press the opposite key
to fine tune. When the meter displays the desired equalize time (in hours),
release the
UP
If you set the equalize time to zero hours, the equalize mode is disabled.
• Press the
internally. The same timer setting works for both the manual timer and
the auto-equalize timer.
If you want to adjust the alarm settings, skip to Section 2.3.4.
If you want to exit the Edit Mode now, press the
more times until the AT30 returns to normal operation.

2.3.4. Setting the Alarms

After you save the equalize timer setting, the Edit Mode automatically
prompts you to adjust the settings of the high dc voltage and low dc
voltage alarms. There is a red indicator light on the front instrument panel
of the AT30 for each of the following alarm conditions:
• High DC Voltage
• Low DC Voltage
• DC Output Failure
• AC Input Failure
• Positive (+) Ground Fault Detection
• Negative (-) Ground Fault Detection
When an alarm occurs, the indicator LEDs will light immediately. The
AT30 also features a summary alarm relay with one (1) form-C remote
contacts (TB3), rated 0.5A / 125 Vac/Vdc. If an alarm condition lasts for
30 seconds or longer, the summary alarm relay contacts transfer. When
the alarm condition is corrected, the relay and all indicators reset
automatically. If latching alarms/relays are enabled the relay will need to
be reset manually, see Section 2.2.7 on page 29.
The summary alarm relay also transfers when the AT30 detects certain
secondary errors, indicated by meter display codes rather than a discrete
front panel red LED. Codes E 01 through E 13, and A 01 will trigger the
summary alarm. See Section 3.2 on page 45 for all error and status codes.
32
key until the EQLZ HRS REMAINING,
EDIT/ENTER
or
UP
DOWN
or
key. The maximum value is 255 hours.
DOWN
key. The new equalize timer duration is saved
EDIT/ENTER
OR
key to increase or decrease the value on
EDIT/ENTER
key three (3)