Auxiliary Alarm Relay Pc Board (Optional) - HindlePower AT30 SERIES Operating And Service Instructions

Microprocessor-controlled float battery charger three phase input (25 - 1,000 adc)
Table of Contents

Advertisement

Auxiliary Alarm Relay PC Board (optional)

The optional Auxiliary Alarm Relay PC Board (A5), mounted on plastic
stand-offs inside the enclosure, provides two (2) form-C contacts (TB4-1
through TB4-36) for each of the following individual alarms:
• High DC Voltage
• Low DC Voltage
• DC Output Failure
• AC Input Failure
• Ground Fault Detection (positive or negative)
• Summary (common) Alarm
Alarm contacts (TB4A/B), marked in non-alarm condition, are as follows:
HVDC
HVDC
LVDC
C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO
1 2 3
4 5 6
7 8 9
PROCEDURE
1. De-energize and lock out all ac and dc voltages to the AT30.
2. Allow internal voltages to dissipate, then check with a voltmeter.
3. Remove the Plexiglas safety shield (if supplied).
4. Route your remote annunciator wiring into the enclosure through one of the
unused conduit knockouts on the side of the enclosure.
5. As shown in the figure above, connect the wiring (use #22-14 AWG) to the
appropriate terminals of TB4 on the Auxiliary Alarm Relay PC Board (A5).
6. Strip each wire 0.25in / 6.4mm and securely tighten the terminal screws.
7. Replace the safety shield, if supplied, and restart the AT30.
NOTES
1. Alarm contacts are rated at 0.5A / 125 Vac or Vdc.
2. Terminal block (TB4) is compression type, accepting #22-14 AWG wire.
3. Terminals are labeled in non-alarm condition.
4. For a detailed view of the optional Auxiliary Alarm Relay PC Board (A5),
refer to drawing (JE5091-39) listed in Appenix C on Page 78.
DC OUT
DC OUT
LVDC
FAILURE
FAILURE
AC FAIL
10 11 12 13 14 15
16 17 18 19 20 21
INSTALLING THE AT30
GROUND
GROUND
AC FAIL
DETECT
DETECT SUM M ARYSUM M ARY
22 23 24
25 26 27 28 29 30
31 32 33 34 35 36
19

Advertisement

Table of Contents
loading

Table of Contents