MMI-20025166

17.13.29 [111] Frequency Output 1 Fixed

Alert
Output Fixed
Cause
The output is configured to send a constant value. A loop test may be in progress.
Recommended actions
Check to see if a loop test is in process (the output is fixed).

17.13.30 [113] mA Output 2 Saturated

Alert
Output Saturated
Cause
The calculated output value is outside the range of the output.
Recommended actions
1. Check the settings of Upper Range Value and Lower Range Value.
Refer to
Configure Lower Range Value (LRV) and Upper Range Value (URV) for the mA
2. Check your process conditions against the values reported by the device.
3. Ensure that both devices are using the same measurement unit.
4. Purge the sensor tubes.

17.13.31 [114] mA Output 2 Fixed

Alert
Output Fixed
Cause
The output is configured to send a constant value. A loop test may be in progress.
Recommended actions
1. Check to see if a loop test is in process (the output is fixed).
2. Exit the mA Output trim, if applicable.

17.13.32 [115] External Input Error

Alert
Process Aberration
Configuration and Use Manual
Troubleshooting
March 2019
Output.