[123] Pressure Overrange (Api Referral); [131] Smart Meter Verification In Progress; [132] Sensor Simulation Active; [138] Tbr Active - Emerson Micro Motion 5700 Configuration And Use Manual

Transmitters with configurable outputs
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Troubleshooting
March 2019
Recommended actions
Check to see if a loop test is in process (the output is fixed).

17.13.40 [123] Pressure Overrange (API referral)

Alert
Process Aberration
Cause
The line pressure is outside the range of the API table.
Recommended actions
1. Ensure that process pressure is within the range of the API table.
2. Verify the configuration of the API referral application and related parameters.

17.13.41 [131] Smart Meter Verification in Progress

Alert
Function Check in Progress
Cause
A Smart Meter Verification test is running.
Recommended actions
Allow the test to complete.

17.13.42 [132] Sensor Simulation Active

Alert
Sensor Being Simulated
Cause
Sensor simulation mode is enabled (enhanced core processor only).
Recommended actions
Disable sensor simulation.

17.13.43 [138] TBR Active

Alert
Process Aberration
Cause
Drive gain is above the configured threshold and transient bubble remediation is active.
276
Micro Motion Model 5700 Transmitters with Configurable Outputs
Configuration and Use Manual
MMI-20025166