Emerson Micro Motion 5700 Configuration And Use Manual page 103

Transmitters with configurable outputs
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Configuration and Use Manual
MMI-20025166
Compensation Off
The transmitter sends the close command when the measured batch total reaches
the configured target.
Fixed
The transmitter sends the close command when the measured batch total equals the
Compensation
target minus the value configured for Fixed Overshoot Compensation. This value is
Value
configured in the current mass or volume unit, and applies to all presets.
AOC Algorithm
The transmitter compares the actual measured amount of each batch to the batch
target, and determines the adjustment by calibrating itself according to an internal
algorithm. You can choose to stop AOC calibration when you are satisfied with the
result, or you can set up rolling (continuous) AOC calibration.
Procedure
To use the Compensation Off option:
a) Choose Configure > Manual Setup > Inputs/Outputs > Batcher > Batcher.
b) Set Compensation Mode to No Compensation.
To use the Fixed Compensation Value option:
a) Choose Configure > Manual Setup > Inputs/Outputs > Batcher > Batcher.
b) Set Compensation Mode to Fixed Value.
c) Set Fixed AOC Value to the quantity to be subtracted from the batch target.
Important
Adjust the fixed value:
Whenever the process changes (e.g., flow rate, process fluid)
Whenever you change any configuration parameter that can affect flow measurement (e.g., damping)
To use the AOC Algorithm option:
a) Choose Configure > Manual Setup > Inputs/Outputs > Batcher > Batcher.
b) Set Compensation Mode to AOC.
c) Perform AOC calibration.
Restriction
You cannot perform AOC calibration using the Field Communicator. AOC calibration requires running
several batches, and you cannot run batches using the Field Communicator.
Configuration and Use Manual
Configure process measurement applications
March 2019
103

Advertisement

Table of Contents
loading

Table of Contents