You can specify the precision (the number of decimal places) that the display uses for each display variable.
You can set the precision independently for each display variable.
The display precision does not affect the actual value of the variable, the value used in calculations, or the
value reported via outputs or digital communications.
Procedure
1. Select a process variable or a diagnostic variable.
You can configure the precision for all variables, whether or not they are assigned as display variables.
The configured precision will be stored and used when applicable.
2. Set Number of Decimal Places to the number of decimal places to be used when this variable is shown
on the display.
Default:
Temperature variables: 2
All other variables: 4
Range: 0 to 5
Tip
The lower the precision, the greater the change must be for it to be reflected on the display. Do not set
Number of Decimal Places too low to be useful.
7.1.4 Turn on and turn off automatic scrolling through the display
variables
Menu > Configuration > Display Settings > Auto Scroll
Display
Device Tools > Configuration > Transmitter Display > General > Auto Scroll
ProLink III
Configure > Manual Setup > Display > Display Behavior > Auto Scroll
Field Communicator
You can configure the display to automatically scroll through the list of display variables or to show a single
display variable until the operator activates Scroll. If Auto Scroll is turned on, you can configure the number
of seconds that each display variable will be shown.
Procedure
1. Turn on or turn off Auto Scroll as desired.
Option Description
On
The display automatically shows each display variable for the number of seconds specified
by Scroll Rate, then shows the next display variable. The operator can move to the next
display variable at any time by activating Scroll.
Off
The display shows Display Variable 1 and does not scroll automatically. The operator can
move to the next display variable at any time by activating Scroll.
Default: Off