Configure advanced options for process measurement
March 2019
6.7.2 Interaction between Process Variable Fault Action and other
fault actions
The setting of Process Variable Fault Action affects the operation of the mA Outputs, Frequency Outputs,
and Discrete Outputs if the corresponding output fault actions are set to None.
Interaction between Process Variable Fault Action and mA Output Fault Action
If mA Output Fault Action is set to None, the mA Output signal depends on the setting of Process Variable
Fault Action.
If the device detects a fault condition:
1. Process Variable Fault Action is evaluated and applied.
2. mA Output Fault Action is evaluated.
If it is set to None, the output reports the value associated with the setting of Process Variable
Fault Action.
If it is set to any other option, the output performs the specified fault action.
If you want the mA Output to continue to report process data during fault conditions, you must set both mA
Output Fault Action and Process Variable Fault Action to None.
Interaction between Process Variable Fault Action and Frequency Output Fault Action
If Frequency Output Fault Action is set to None, the Frequency Output signal depends on the setting of
Process Variable Fault Action.
If the device detects a fault condition:
1. Process Variable Fault Action is evaluated and applied.
2. Frequency Output Fault Action is evaluated.
If it is set to None, the output reports the value associated with the setting of Process Variable
Fault Action.
If it is set to any other option, the output performs the specified fault action.
If you want the Frequency Output to continue to report process data during fault conditions, you must set
both Frequency Output Fault Action and Process Variable Fault Action to None.
Interaction between Process Variable Fault Action and Discrete Output Fault Action
If Discrete Output Fault Action is set to None and Discrete Output Source is set to Flow Rate Switch, the
discrete output state during a fault depends on the setting of Process Variable Fault Action.
If the device detects a fault condition:
1. Process Variable Fault Action is evaluated and applied.
2. Discrete Output Fault Action is evaluated.
If it is set to None, and Discrete Output Source is set to Flow Rate Switch, the discrete output will
use the value determined by the current setting of Process Variable Fault Action to determine if a
flow rate switch has occurred.
116
Micro Motion Model 5700 Transmitters with Configurable Outputs
Configuration and Use Manual
MMI-20025166