Operation using the batcher
March 2019
b) Click Start AOC Calibration.
c) Run several batches, allowing each batch to run to completion, and observe the totals.
d) When batch repeatability meets requirements, click Save AOC Calibration.
AOC calibration is stopped, and the current coefficient is saved.
Important
If you are using a saved value, repeat AOC calibration:
Whenever the fluid characteristics change, especially viscosity
Whenever you change any configuration parameter that can affect flow measurement (e.g., damping)
To set up rolling calibration:
a) Choose Device Tools > Configuration > Batcher.
b) Set AOC Window Length to the number of batches that the rolling AOC coefficient will be based
on.
c) Choose Device Tools > Application Control > Run Batcher.
d) Click Start AOC Calibration.
Important
If you are using rolling calibration, and fluid characteristics change or the transmitter configuration
changes, the transmitter will automatically adjust to the new conditions after a few batches.
198
Micro Motion Model 5700 Transmitters with Configurable Outputs
Configuration and Use Manual