Configuration and Use Manual
MMI-20025166
Procedure
Set mA Output Direction as desired.
Option
Description
Normal (default) Appropriate when your application needs to distinguish between forward flow and
reverse flow.
Absolute Value
Appropriate when your application does not need to distinguish between forward flow
and reverse flow.
Important
mA Output Direction interacts with Lower Range Value (LRV). The effect of mA Output Direction on the mA
Output varies, depending on whether LRV < 0 or LRV ≥ 0.
Related information
Configure Sensor Flow Direction Arrow
Effect of mA Output Direction on an mA Output
mA Output Direction affects how the transmitter reports flow values via an mA Output. An mA Output is
affected by mA Output Direction only if mA Output Source is set to a flow variable.
The effect of mA Output Direction depends on the setting of Lower Range Value (LRV).
If Lower Range Value = 0, see
•
•
If Lower Range Value > 0, see
•
If Lower Range Value < 0, see
Configuration and Use Manual
Figure
8-1.
Figure 8-1
and adapt the chart.