Consistently Incorrect Fo Measurement - Emerson Micro Motion 5700 Configuration And Use Manual

Transmitters with configurable outputs
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Troubleshooting
March 2019
Fault condition if Fault Action is set to Internal Zero or Downscale
Two-phase flow
Flow in reverse direction from configured flow direction parameter
Frequency Output Direction not set correctly
Bad frequency receiving device
Output level not compatible with receiving device
Bad output circuit
Incorrect internal/external power configuration
Output not powered
Wiring problem
Channel not configured for desired output
Channel not configured for desired input
Channel not licensed
Recommended actions
1. Verify that the process conditions are below the low-flow cutoff. Reconfigure the low-flow cutoff if
necessary.
2. Check the Fault Action settings.
3. Verify that the totalizers are not stopped. A stopped totalizer will cause the Frequency Output to be
locked.
4. Check for two-phase flow.
5. Check flow direction.
6. Check the direction parameters.
7. Verify the receiving device, and the wiring between the transmitter and the receiving device.
8. Verify that the channel is wired and configured as a Frequency Output.
9. Purchase a license for the channel and upgrade the transmitter firmware.
10. Verify the power configuration for the Frequency Output (internal vs. external).
11. Perform a loop test.

17.10.2 Consistently incorrect FO measurement

Cause
Output not scaled correctly
Incorrect measurement unit configured for process variable
Recommended actions
1. Check the scaling of the Frequency Output.
2. Verify that the measurement units are configured correctly for your application.
256
Micro Motion Model 5700 Transmitters with Configurable Outputs
Configuration and Use Manual
MMI-20025166