Configure process measurement applications
March 2019
Need help?
If the value is not correct:
Ensure that the external device and the meter are using the same measurement unit.
For polling:
Verify the wiring between the meter and the external device.
Verify the HART tag of the external device.
For the mA Input:
Verify the wiring between the meter and the external device.
Verify the power configuration for Channel D. If external power is required, ensure that the loop is
powered.
Verify the Lower Range Value and Upper Range Value settings for the mA Input.
Perform an mA Input trim.
Adjust the mA Input damping value.
For digital communications:
Verify that the host has access to the required data.
Verify that the host is writing to the correct register in memory, using the correct data type.

Modify matrix names and labels using the display

For convenience, you can change the name of a concentration matrix and the label used for its measurement
unit. This does not affect measurement.
Procedure
1. Choose Menu > Configuration > Process Measurement > Concentration Measurement > Configure
Matrix.
2. Select the matrix that you want to modify.
3. Set Matrix Name to the name that will be used for this matrix.
4. Set Concentration Unit to the label that will be used for the concentration unit.
If you want to use a custom label, you can use the display to select Special. However, you cannot use
the display to configure the custom label. You must use another tool to change the label from Special
to a user-defined string.
Modify extrapolation alerts for concentration measurement using the
display
You can enable and disable extrapolation alerts, and set extrapolation alert limits. These parameters control
the behavior of the concentration measurement application but do not affect measurement directly.
Each concentration matrix is built for a specific density range and a specific temperature range. If line density
or line temperature goes outside the range, the transmitter will extrapolate concentration values. However,
extrapolation may affect accuracy. Extrapolation alerts are used to notify the operator that extrapolation is
occurring.
Each concentration matrix has its own extrapolation alert limits.
78
Micro Motion Model 5700 Transmitters with Configurable Outputs
Configuration and Use Manual