Integrate the meter with the control system
March 2019
Before changing the channel configuration, ensure that all control loops affected by the channel are under
manual control.
Procedure
1. Identify the channels that are activated on your device.
2. For Channel B, Channel C, and Channel D, if activated, set Channel Type as desired.
Channel
Channel B
Channel C
Channel D
Restriction
You cannot configure Channel Type for Channel A and Channel E. Channel A is always mA Output 1.
Channel E is always RS-485.
Note
If both Channel B and Channel D are set to operate as Frequency Output 2, the Frequency Output 2
configuration is applied to both channels, and their behavior is identical.
3. For each activated channel except Channel E, set Power Source as desired.
Option
Internal (Active)
External (Passive)
Restriction
You cannot configure Power Source for Channel E.
Postrequisites
For each channel that you configured, perform or verify the corresponding output or input configuration.
When the configuration of a channel is changed, the channel's behavior will be controlled by the
136
Options
mA Output 2 (default)
Frequency Output 2
Discrete Output 1
mA Output 3
Frequency Output 1 (default)
Discrete Output 2
Discrete Input 1
Frequency Output 2
Discrete Output 3 (default)
Discrete Input 2
mA Input
Frequency Input
Description
The channel is powered by the transmitter.
The channel is powered by an external power source.
Micro Motion Model 5700 Transmitters with Configurable Outputs
Configuration and Use Manual
MMI-20025166