Configure process measurement applications
March 2019
Method
Description
mA Input
An external device sends
temperature data to the meter
via the mA Input. This data will
be available in addition to the
internal temperature data.
Digital
A host writes temperature data
communications
to the meter at appropriate
intervals. This data will be
available in addition to the
internal temperature data.
2. (A, B, C, and D tables only) Choose the method to be used to supply pressure data, and perform the
required setup.
56
Setup
a. Choose Menu > Configuration > Process Measurement >
Temperature.
b. Set External Temperature to On.
c. Choose Menu > Configuration > Inputs/Outputs > Channel
D.
d. Set I/O Type to MAI.
e. Set Power appropriately.
f. Choose I/O Settings.
g. Set Assignment to External Temperature.
h. Set Lower Range Value and Upper Range Value
appropriately.
a. Choose Menu > Configuration > Process Measurement >
Temperature.
b. Set External Temperature to On.
c. Perform the necessary host programming and
communications setup to write temperature data to the
transmitter at appropriate intervals.
Micro Motion Model 5700 Transmitters with Configurable Outputs
Configuration and Use Manual
MMI-20025166