Configure A Do For Valve Control Using Prolink Iii - Emerson Micro Motion 5700 Configuration And Use Manual

Transmitters with configurable outputs
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Configuration and Use Manual
MMI-20025166
Procedure
1. Verify the wiring between the selected channel and the valve.
2. Configure the selected channel to operate as a Discrete Output.
a) Choose Menu > Configuration > Inputs/Outputs.
b) Set Channel B, Channel C, or Channel D to operate as a Discrete Output.
c) Set Power Source to External.
3. Configure the selected channel for valve control.
a) Choose Menu > Configuration > Inputs/Outputs.
b) Select the discrete output to be used for valve control.
c) Choose I/O Settings.
d) Set Source to Batch Primary Valve.
e) Set Polarity to match the wiring.
The ON state of the Discrete Output must open the valve, and the OFF state must close the
valve.
f) Set Fault Action so that the valve will be closed if a fault occurs.
The appropriate setting is either Upscale or Downscale. The setting to use for your installation
depends on your valve type, your wiring, and your setting for Polarity.
4. Optional: For two-stage batching, assign one of the discrete outputs to the secondary valve.
You can also assign one of the Discrete Outputs to a pump when the batcher is configured for single
stage or two stage.

Configure a DO for valve control using ProLink III

Prerequisites
Channel B, Channel C, or Channel D must be available for valve control.
The selected channel must be wired to the valve.
The selected channel and the valve must be powered by a power supply, not by the transmitter.
Procedure
1. Verify the wiring between the selected channel and the valve.
2. Configure the selected channel to operate as a Discrete Output.
a) Choose Device Tools > Configuration > I/O > Channels.
b) Set Channel B, Channel C, or Channel D to operate as a Discrete Output
c) Set Power Source to External.
3. Configure the selected channel for valve control.
a) Choose Device Tools > Configuration > I/O > Outputs > Discrete Output.
Configuration and Use Manual
Configure process measurement applications
March 2019
99