Options For Mao Fault Action And Mao Fault Level - Emerson Micro Motion 5700 Configuration And Use Manual

Transmitters with configurable outputs
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Integrate the meter with the control system
March 2019
ProLink III
Device Tools > Configuration > I/O > Outputs > mA Output x > Fault Action
Field Communicator
Configure > Manual Setup > Inputs/Outputs > Channel x > mA Output x > mAOxFault Settings > mAOx
Fault Action
mA Output Fault Action controls the behavior of the mA Output if the transmitter detects a fault condition.
Important
The fault action is implemented only if Alert Severity is set to Failure. If Alert Severity is set to any other
option, the fault action is not implemented.
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement the
fault action until the timeout has elapsed.
Procedure
1. Set mA Output Fault Action as desired.
Default: Downscale
Important
If you set mA Output Fault Action to None, the mA Output will be controlled by the setting of Process
Variable Fault Action. In most cases, if you set mA Output Fault Action to None, you should also set
Process Variable Fault Action to None.
2. If you set mA Output Fault Action to Upscale or Downscale, set mA Output Fault Level to the signal
that the mA Output will produce during a fault.
Related information
Configure Process Variable Fault Action
Interaction between Process Variable Fault Action and other fault actions

Options for mAO Fault Action and mAO Fault Level

Option
Upscale
Downscale (default)
Internal Zero
None
146
mA Output behavior
Goes to the configured fault level
Goes to the configured fault level
Goes to the mA Output level associated with a
process variable value of 0 (zero), as determined
by Lower Range Value and Upper Range Value
settings
Determined by the setting of Process Variable
Fault Action
Micro Motion Model 5700 Transmitters with Configurable Outputs
Configuration and Use Manual
MMI-20025166
mA Output Fault Level
Default: 22.0 mA
Range: 21.0 to 23.0 mA
Default: 2.0 mA
Range: 1.0 to 3.6 mA
Not applicable
Not applicable