Function Block Space Heating; Operating Lines; Settings And Displays - Siemens RVD240 Basic Documentation

District heating and domestic hot water controller
Table of Contents

Advertisement

28/126
Siemens Building Technologies
HVAC Products
5

Function block Space heating

This function block contains settings and readouts that are intended for the end-user.
5.1

Operating lines

The buttons for selecting the operating lines and for changing settings are described in
section 31.1 "Operation ".
Line
Function, parameter
1
Current room temperature setpoint
2
Reduced room temperature setpoint
3
Setpoint for frost protection / holiday mode
5
Heating curve slope
6
Weekday for entering the heating program
7
Start of heating period 1
8
End of heating period 1
9
Start of heating period 2
10
End of heating period 2
11
Start of heating period 3
12
End of heating period 3
Notes on settings and explanations on every function block are given in the descrip-
tions of the individual functions.
5.2

Settings and displays

• The nominal room temperature setpoint is adjusted with the setpoint knob. Its scale
is calibrated in °C room temperature. The room temperature will be maintained at the
adjusted setpoint:
In automatic operation during the heating periods
In continuous operation
• On operating line 1, the LCD shows the current room temperature setpoint of each
heating circuit Depending on the operating mode and the operating state, the room
temperature setpoint can be:
Operating mode and operat-
ing state
Heating to the nominal set-
point
Heating to the reduced set-
point
Continuous operation
Quick setback
Frost protection
OFF by ECO
• The reduced room temperature setpoint of each heating circuit is to be set sepa-
rately on operating line 2; at the top, the setting range is limited by the nominal set-
point; at the bottom, by the setpoint for frost protection. This is the setpoint main-
tained outside the heating periods
• The setpoint for frost protection of each heating circuit is to be set separately on
operating line 3; the setting range is from 8 °C (fixed value) to the adjusted reduced
setpoint. Hence, this frost protection acts as frost protection for the house or building.
At the same time, this setting represents the setpoint for the holiday mode. A holiday
program can be entered either on the controller or on the QAW70 room unit. For
Basic documentation RVD240
5 Function block Space heating
Unit
Factory setting
°C
°C
Current weekday
hh:min
hh:min
hh:min
hh:min
hh:min
hh:min
always
Displayed setpoint
Adjustment made with the setting knob (incl. the
readjustment made on the room unit)
Reduced setpoint (setting operating line 2)
Adjustment made with the setpoint knob
Reduced setpoint (setting operating line 2)
Setpoint for frost protection (setting operating line 3)
• During heating periods: adjustment made with
the setting knob (incl. the readjustment made on
the room unit)
• Outside heating periods: Reduced setpoint
Range
Display function
14
variable
8
8...variable
15
2.5...40
1...7, 1-7
06:00
--:-- / 00:00...24:00
22:00
--:-- / 00:00...24:00
--:--
--:-- / 00:00...24:00
--:--
--:-- / 00:00...24:00
--:--
--:-- / 00:00...24:00
--:--
--:-- / 00:00...24:00
CE1P2384en
27.05.2004