Autoreclose In Progress Logic Diagram For Cb2; Sequence Counter; Figure 164: Autoreclose In Progress Logic Diagram For Cb2 (Module 17) - GE MiCOM P40 Technical Manual

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

Chapter 11 - Autoreclose
5.9.2

AUTORECLOSE IN PROGRESS LOGIC DIAGRAM FOR CB2

Init AR
CB2 Ext Trip A
CB2 Ext Trip B
CB2 Ext Trip C
CB2 Ext Trip 3ph
CB2 TMEM2/3 Ph
CB2 TMEM1Ph
CB2 Op2/3P
CB2L3 PAROK
CB2 F3 PAROK
Inhibit AR
CB2 LO Alarm
CB2 NoAR
CB2 ARSUCC
CBARCancel
CB2 OpAny
CB2 ARIP
AR Start
Set CB2 Close
CB2 Closed 3 ph
Leader CB2
Follower CB2
V03324

Figure 164: Autoreclose In Progress logic diagram for CB2 (Module 17)

5.10

SEQUENCE COUNTER

The Autoreclose logic includes a counter for counting the number of Autoreclose shots. This is referred to as the
sequence counter. The sequence counter has a value of zero if Autoreclose is not in progress. Following a trip, and
subsequent Autoreclose initiation, the sequence counter is incremented. The counter provides output signals
indicating how many initiation events have occurred in any Autoreclose cycle. These signals are available as user
indications and are used in the logic to select the appropriate dead times or, for a persistent fault, force a lockout.
It is possible to skip the first Autoreclose attempt by enabling the AR Skip Shot 1 setting. If this is set, the sequence
counter will skip the first Autoreclose attempt (Shot 1) and move to the second (Shot 2) immediately upon
Autoreclose initiation. Each time the protection trips the sequence counter is incremented by 1. The Autoreclose
logic compares the sequence counter value to the number of Autoreclose shots setting AR Shots. If the counter
value exceeds this setting then the Autoreclose is locked out. If Autoreclose is successful, the sequence counter
resets to zero.
304
1
1
&
&
1
0.02
0
&
1
&
&
1
&
S
Q
R
1
P446SV
CB2 AR Init
CB2 ARIP
&
CB2 LARIP
&
CB2 FARIP
P446SV-TM-EN-1