GE MiCOM P40 Technical Manual page 777

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
MENU TEXT
Phase angle difference between selected phase ("C/S Input" 0A 0F) of Line VT input and applied "CB2 CS" VT input voltage under healthy
system conditions
CB2 CS VT Mag
Ratio of voltage magnitudes of selected phase ("C/S Input" 0A 0F) of Line VT input and applied "CB2 CS" VT input voltage under healthy
system conditions
RECORD CONTROL
This column contains settings for Record Controls
Alarm Event
Disabling this setting means that all the occurrences that produce an alarm will result in no event being generated.
Relay O/P Event
Disabling this setting means that no event will be generated for any change in logic state.
Opto Input Event
Disabling this setting means that no event will be generated for any change in logic input state.
General Event
Disabling this setting means that no General Events will be generated
Fault Rec Event
Disabling this setting means that no event will be generated for any fault that produces a fault record
Maint Rec Event
Disabling this setting means that no event will be generated for any occurrence that produces a maintenance record.
Protection Event
Disabling this setting means that any operation of protection elements will not be logged as an event
DDB 31 - 0
Chooses whether any individual DDBs should be deselected as a stored event, by setting the relevant bit to 0 (zero). Typically used for
repetitive recurrent changes such as an Opto input assigned for Minute Pulse clock synchronizing.
DDB 63 - 32
Chooses whether any individual DDBs should be deselected as a stored event, by setting the relevant bit to 0 (zero). Typically used for
repetitive recurrent changes such as an Opto input assigned for Minute Pulse clock synchronizing.
DDB 95 - 64
Chooses whether any individual DDBs should be deselected as a stored event, by setting the relevant bit to 0 (zero). Typically used for
repetitive recurrent changes such as an Opto input assigned for Minute Pulse clock synchronizing.
DDB 127 - 96
Chooses whether any individual DDBs should be deselected as a stored event, by setting the relevant bit to 0 (zero). Typically used for
repetitive recurrent changes such as an Opto input assigned for Minute Pulse clock synchronizing.
DDB 159 - 128
Chooses whether any individual DDBs should be deselected as a stored event, by setting the relevant bit to 0 (zero). Typically used for
P446SV-TM-EN-1
COL
ROW
DEFAULT SETTING
0A
24
1
0B
00
0B
04
Enabled
0B
05
Enabled
0B
06
Enabled
0B
07
Enabled
0B
08
Enabled
0B
09
Enabled
0B
0A
Enabled
0B
40
0xFFFFFFFF
0B
41
0xFFFFFFFF
0B
42
0xFFFFFFFF
0B
43
0xFFFFFFFF
0B
44
0xFFFFFFFF
DESCRIPTION
From 0.2 to 3 in steps of 0.01
[Courier Number]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
High order word of long stored in 1st register
Low order word of long stored in 2nd register
[Binary Flag (32-Bit)]
High order word of long stored in 1st register
Low order word of long stored in 2nd register
[Binary Flag (32-Bit)]
High order word of long stored in 1st register
Low order word of long stored in 2nd register
[Binary Flag (32-Bit)]
High order word of long stored in 1st register
Low order word of long stored in 2nd register
[Binary Flag (32-Bit)]
High order word of long stored in 1st register
Low order word of long stored in 2nd register
[Binary Flag (32-Bit)]
Appendix B -Settings and Signals
AVAILABLE OPTIONS
B31