GE MiCOM P40 Technical Manual page 307

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
Signal Name
CB2CRLo
CB In Service (4)
CB2F3PAR
CB2F3PAROK
AR Modes Enable (9)
1-phase AR Cycle Selection
CB2FSPAR
(19)
CB2FSPAROK
AR Modes Enable (9)
3-phase AR cycle selection
CB2L3PAR
(21)
CB2L3PAROK
AR Modes Enable (9)
Leader/Follower
CB2LFRC
Logic 1 & 2 (7)
1-phase AR Cycle Selection
CB2LSPAR
(19)
CB2LSPAROK
AR Modes Enable (9)
CB2SPDTComp
1-phase AR Dead Time (24)
Follower 1-phase CB AR
CB2SPFTComp
Time (28)
DeadLineLockout
Dead Time Start Enable (22) Autoreclose Lockout (55)
ENABLE CB13PDT
ENABLE CB1SPDT
ENABLE CB23PDT
ENABLE CB2SPDT
EvolveLock
Evolving Fault (20)
F Out of Range
FltMem2P
Fault Memory (15)
FltMem3P
Fault Memory (15)
Foll3PAROK
AR Modes Enable (9)
P446SV-TM-EN-1
Source
1-phase AR Cycle Selection (19)
Follower CB AR Enable (27)
Follower 3-phase CB AR Time (29)
CB2 AR In Progress (17)
3-phase AR cycle selection (21)
Follower CB AR Enable (27)
Follower 1-phase CB AR Time (28)
Follower 3-phase CB AR Time (29)
Force 3-phase Trip (10)
1-phase AR Cycle Selection (19)
3-phase AR cycle selection (21)
1-phase AR Cycle Selection (19)
CB2 AR In Progress (17)
3-phase AR cycle selection (21)
Leader/Follower (7)
Follower 1-phase CB AR Time (28)
Follower 3-phase CB AR Time (29)
Reclaim Time (35)
Autoreclose Lockout (55)
AR Modes Enable (9)
1-phase AR Cycle Selection (19)
1-phase AR Dead Time (24)
AR Modes Enable (9)
1-phase AR Cycle Selection (19)
3-phase AR cycle selection (21)
Autoreclose Lockout (55)
Check Sync Signals (60)
Autoreclose Lockout (55)
Autoreclose Lockout (55)
Leader/Follower (7)
AR Modes Enable (9)
Destination
Reset lockout for CB2
Three-phase Autoreclose is in progress for
CB2 as a follower
CB2 is OK to perform three-phase
Autoreclose as follower
Single-phase Autoreclose is in progress for
CB2 as follower
CB2 is OK to perform single-phase
Autoreclose as follower
Three-phase Autoreclose is in progress for
CB2 as leader
CB2 is OK to perform three-phase
Autoreclose as leader
CB2 failed to reclose as leader
Single-phase Autoreclose is in progress for
CB2 as leader
CB2 is OK to perform single-phase
Autoreclose as leader
CB2 single-phase dead time is complete
CB2 single-phase follower time is complete
Signal to force the auto-reclose sequence
to lockout
Enable dead time for three-phase
Autoreclose for CB1
Enable dead time for single-phase
Autoreclose for CB1
Enable dead time for three-phase
Autoreclose for CB2
Enable dead time for single-phase
Autoreclose for CB2
Lockout for 2nd trip after the "Discrim
Time" has expired
Signal from the frequency tracking logic
indicating that the measured power system
frequency is outside the operational range
A signal to indicate that the initiating fault
involved 2 phases
A signal to indicate that the initiating fault
involved 3 phases
The follower circuit breaker is Ok for three-
phase Autoreclose
Chapter 11 - Autoreclose
Description
275

Advertisement