GE MiCOM P40 Technical Manual page 925

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
ORDINAL
912
CB2 Open A ph
Circuit breaker 2 A phase is open
913
CB2 Open B ph
Circuit breaker 2 A phase is open
914
CB2 Open C ph
Circuit breaker 2 A phase is open
915
CB2 Closed 3 ph
Circuit breaker 2 is closed, all three phases
916
CB2 Closed A ph
Circuit breaker 2 A phase is closed
917
CB2 Closed B ph
Circuit breaker 2 B phase is closed
918
CB2 Closed C ph
Circuit breaker 2 C phase is closed
919
Inhibit Cmp V1>1
Inhibit the first stage compensated overvoltage element
920
Inhibit Cmp V1>2
Inhibit the second stage compensated overvoltage element
921
Cmp V1>1 Tim Blk
Block the first stage compensated overvoltage element
922
Cmp V1>2 Tim Blk
Block the second stage compensated overvoltage element
923
V1>1 Cmp Start
1st stage compensated overvoltage start signal
924
V1>2 Cmp Start
2nd stage compensated overvoltage start signal
925
V1>1 Cmp Trip
1st stage compensated overvoltage trip signal
926
V1>2 Cmp Trip
2nd stage compensated overvoltage trip signal
928
CTS Block
Standard or differential CT supervision block (current transformer supervision)
952
Faulted Phase A
Faulted phase A - must be assigned, as this sets the start flag used in records, and on the LCD display
953
Faulted Phase B
Faulted phase B - must be assigned, as this sets the start flag used in records, and on the LCD display
954
Faulted Phase C
Faulted phase C - must be assigned, as this sets the start flag used in records, and on the LCD display
955
Faulted Phase N
Faulted phase N (fault involves ground) - must be assigned, as this sets the start flag used in records, and on the LCD display
956
Started Phase A
Started phase A - must be assigned, as this sets the start flag used in records, and on the LCD display
957
Started Phase B
Started phase B - must be assigned, as this sets the start flag used in records, and on the LCD display
958
Started Phase C
Started phase C - must be assigned, as this sets the start flag used in records, and on the LCD display
959
Started Phase N
Started phase N (fault involves ground) - must be assigned, as this sets the start flag used in records, and on the LCD display
960
Zone1 AN Element
Zone 1 AN ground fault element
961
Zone1 BN Element
Zone 1 BN ground fault element
962
Zone1 CN Element
Zone 1 CN ground fault element
963
Zone1 AB Element
Zone 1 AB phase fault element
964
Zone1 BC Element
Zone 1 BC phase fault element
P446SV-TM-EN-1
SIGNAL NAME
DDB_CB2_PHASE_A_OPEN
DDB_CB2_PHASE_B_OPEN
DDB_CB2_PHASE_C_OPEN
DDB_CB2_CLOSED
DDB_CB2_PHASE_A_CLOSED
DDB_CB2_PHASE_B_CLOSED
DDB_CB2_PHASE_C_CLOSED
DDB_INHIBIT_COMP_OV1
DDB_INHIBIT_COMP_OV2
DDB_PCOV_1_TIMER_BLOCK
DDB_PCOV_2_TIMER_BLOCK
DDB_PCOV_1_3PH_START
DDB_PCOV_2_3PH_START
DDB_PCOV_1_3PH_TRIP
DDB_PCOV_2_3PH_TRIP
DDB_CTS_BLOCK
DDB_FLTREC_FLT_A
DDB_FLTREC_FLT_B
DDB_FLTREC_FLT_C
DDB_FLTREC_FLT_N
DDB_FLTREC_STRT_A
DDB_FLTREC_STRT_B
DDB_FLTREC_STRT_C
DDB_FLTREC_STRT_N
DDB_ZONE_1_AN
DDB_ZONE_1_BN
DDB_ZONE_1_CN
DDB_ZONE_1_AB
DDB_ZONE_1_BC
ELEMENT NAME
DESCRIPTION
Appendix B -Settings and Signals
B179