Indicates conditions are satisfied to enable CB2 follower sequence
1446
1P Follower Time
Indicates a single pole autoreclose follower time is running (either CB)
1447
3P Follower Time
Indicates a three pole autoreclose follower time is running (either CB)
1448
Auto Close CB2
Signal from autoreclose logic to initiate CB2 close via "CB2 CB Control"
1449
Set CB2 Close
Indicates a CB2 Auto Close signal has been issued
1450
CB2 Control
Output DDB can be applied to inhibit CB2 reclose by adjacent scheme until local autoreclose scheme confirms it is OK to close CB2
1451
CB2 Succ 1P AR
CB2 successful single phase AR
1452
CB2 Succ 3P AR
CB2 successful three phase AR
1453
CB2 Close inProg
CB2 Manual Close initiated – awaiting Man Close Delay time
1454
CB2 Fast SCOK
OK to reclose CB2 with sync check without waiting for dead time to complete
1455
CB2L SCOK
System conditions OK to reclose CB2 as leader when dead time complete
1456
CB2F SCOK
System conditions OK to reclose CB2 when follower time complete
1458
CB2 Man SCOK
System conditions OK to manually close CB2
1459
CB2 Fail Pr Trip
signal to force CB2 AR lockout if CB2 fails to trip when protection operates
1461
Live Bus 2
Indicates Bus 2 input is live, i.e. voltage >= setting [48 89]
1462
Dead Bus 2
Indicates Bus 2 input is dead i.e. voltage < setting [48 8A]
1463
CB2 CS2 OK
CB2 close with synchronism check type 2 is permitted (setting [48 A2]= Enabled), and Line and Bus 2 voltages satisfy relay settings for
CB2 synchronism check type 2
1464
CB1 CS2 SlipF>
Line-Bus 1 slip freq > setting [48 98] (frequency difference (slip) between line voltage and bus 1 voltage is greater than maximum slip
permitted for CB1 synchronism check type 2)
1465
CB1 CS2 SlipF<
Line-Bus 1 slip freq < setting [48 98] (frequency difference (slip) between line voltage and bus 1 voltage is within the permitted range
for CB1 synchronism check type 2)
1466
CB2 CS1 SlipF>
Line-Bus 2 slip freq > setting [48 A1] (frequency difference (slip) between line voltage and bus 2 voltage is greater than maximum slip
permitted for CB2 synchronism check type 1)
1467
CB2 CS1 SlipF<
Line-Bus 2 slip freq < setting [48 A1] (frequency difference (slip) between line voltage and bus 2 voltage is within the permitted range
for CB2 synchronism check type 1)
1468
CB2 CS2 SlipF>
Line-Bus 2 slip freq > setting [48 A6] (frequency difference (slip) between line voltage and bus 2 voltage is greater than maximum slip
permitted for CB2 synchronism check type 2)
1469
CB2 CS2 SlipF<
Line-Bus 2 slip freq < setting [48 A6] (frequency difference (slip) between line voltage and bus 2 voltage is within the permitted range
for CB2 synchronism check type 2)
1470
CB2 CS1 VL>VB
Voltage magnitude difference between Line V and Bus2 V is greater than setting [48 9F] (line V > Bus V)
1471
CB2 CS2 VL>VB
Voltage magnitude difference between Line V and Bus2 V is greater than setting [48 A4] (line V > Bus V)
1472
CB2 CS1 VL<VB
Voltage magnitude difference between Line V and Bus2 V is greater than setting [48 9F] (line V < Bus V)
P446SV-TM-EN-1
SIGNAL NAME
DDB_SPOLE_FOLLOWER_TIME
DDB_3POLE_FOLLOWER_TIME
DDB_CB2_AUTO_CLOSE
DDB_SET_CB2_CLOSE
DDB_CB2_CONTROL
DDB_CB2_SUCCESSFUL_SPAR
DDB_CB2_SUCCESSFUL_3PAR
DDB_CB2_CTRL_CLOSE_IN_PROGRESS
DDB_CB2_FAST_SYSTEM_CHECK_OK
DDB_CB2_LEADER_SYSTEM_CHECK_OK
DDB_CB2_FOLLOWER_SYSTEM_CHECK_OK
DDB_CB2_MANUAL_SYSTEM_CHECK_OK
DDB_CB2_FAIL_PROTECTION_TRIP
DDB_SYSCHECKS_BUS2_LIVE
DDB_SYSCHECKS_BUS2_DEAD
DDB_CHECKSYNC2_2_OK
DDB_CS2_SLIP_O
DDB_CS2_SLIP_U
DDB_CS2_1_SLIP_O
DDB_CS2_1_SLIP_U
DDB_CS2_2_SLIP_O
DDB_CS2_2_SLIP_U
DDB_SYSCHECKS2_1_VLINE_DIFF_HIGH
DDB_SYSCHECKS2_2_VLINE_DIFF_HIGH
DDB_SYSCHECKS2_1_VBUS_DIFF_HIGH
ELEMENT NAME
DESCRIPTION
Appendix B -Settings and Signals
B193

Advertisement

Table of Contents
loading

Table of Contents