Advertisement

P446SV
The impedance on the left side of the right hand resistive line is detected when the angle between S1 and S2 is
greater than 0°.
3.2.2.4
PHASE FAULT REVERSE RESISTIVE REACH LINE
V02726

Figure 52: Reverse resistive reach line construction

For an offset zone, R' is the settable reverse resistive reach (=½*Rx' Ph Res. Rev.). . For a directional zone, R' is fixed
at 25% of the Resistive Reach (=½*Rx Ph Res. Rev.), acting in the opposite direction.
The two signals provided to the comparator are:
S
= V - I.R
1
S
= I.Z
2
The impedance on the right side of the left hand resistive line is detected when the angle between S1 and S2 is less
than 0°.
3.2.2.5
PHASE FAULT QUADRILATERAL CHARACTERISTIC SUMMARY
The phase fault Quadrilateral characteristics are summarised in the following figure and tables:
V02727

Figure 53: Phase Fault Quadrilateral characteristic summary

P446SV-TM-EN-1
+jX
Z
Ð Z
V / I
V / I - R'
R'
+jX
Z
V / I
R'
Z'
Chapter 7 - Distance Protection
+R
R
+R
3°
129