GE MiCOM P40 Technical Manual page 881

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
MENU TEXT
This setting enables CB1 to close by manual control when the live line & dead bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB1M SC DLDB
This setting enables CB1 to close by manual control when the dead line & dead bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2M SC required
This setting determines whether a system check (e.g. live bus / dead line etc) is required for any manual (operator-controlled) closure of CB2.
If Enabled, system check is required for closure. If Disabled, system check is not required.
CB2M SC CS1
This setting enables CB2 to close by manual control when system satisfies all the System Check Synchronism Stage 1 conditions as listed
under the setting CB2 CS1 Status in the SYSTEM CHECKS column.
CB2M SC CS2
This setting enables CB2 to close by manual control when the system satisfies all the System Check Synchronism Stage 2 conditions as listed
under setting CB2 CS2 status in the SYSTEM CHECKS column.
CB2M SC DLLB
This setting enables CB2 to close by manual control when the dead line & live bus2 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2M SC LLDB
This setting enables CB2 to close by manual control when the live line & dead bus2 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2M SC DLDB
This setting enables CB2 to close by manual control when the dead line & dead bus2 conditions are satisfied as set in the SYSTEM CHECKS
column.
GROUP 1:
AUTORECLOSE
This column contains settings for Autoreclose
Num CBs
Setting defines which CB(s) are active for the specific installation: CB1 only, CB2 only or both CB1 & CB2.
AR Mode
If the Num CBs setting (cell 4950 {above} in the AUTORECLOSE column) is set to CB1 Only, or CB2 Only, then this setting determines which
auto-reclose modes are permitted for the circuit breaker : single phase (AR 1P) only, both single phase and three phase (AR 1/3P), three phase
only (AR 3P), or the auto-reclosing mode is controlled by opto input signals (AR Opto) mapped via DDBs (1497) AR Mode 1P and (1498) AR
Mode 3P.
Lead/Foll ARMode
P446SV-TM-EN-1
COL
ROW
DEFAULT SETTING
48
B7
Disabled
48
B8
Disabled
48
B9
Disabled
48
BA
Disabled
48
BB
Disabled
48
BC
Disabled
48
BD
Disabled
49
00
49
50
CB1 Only
49
51
AR 3P
49
53
L 3P, F 3P
DESCRIPTION
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
CB1 Only
CB2 Only
CB1&CB2
[Courier Number]
1P
1/3P
3P
AR Opto
[Indexed String]
L 1P, F 1P
L 1P, F 3P
L 3P, F 3P
L 1/3P, F 1/3P
L 1/3P, F 3P
AR Opto
Appendix B -Settings and Signals
AVAILABLE OPTIONS
B135