P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
ORDINAL
Frequency out of range alarm
320
CB2 Fail Alarm
Circuit breaker 2 fail alarm
321
CB2 Monitor Alm
This alarm indicates that DDB CB2 I ^ Maint. Alarm (1113) or DDB CB2 OPs Maint. (1115) or DDB CB2 Time Maint. (1117)
322
CB2 Mon LO Alarm
This alarm indicates that DDB CB2 I ^ Lockout Alarm (1114) or DDB CB Ops Lock (1116) or DDB CB Time lockout (1118)
323
CB2 Status Alm
Indication of problems by circuit breaker 2 state monitoring - example defective auxiliary contacts
324
CB2 Trip Fail
Circuit breaker 2 failed to trip (after a manual/operator) trip command
325
CB2 Close Fail
Circuit breaker 2 failed to close (after a manual/operator or auto-reclose close command)
326
ManCB2 Unhealthy
Manual circuit breaker unhealthy output signal indicating that the circuit breaker 2 has not closed successfully after a manual close
command. (A successful close also requires The circuit breaker healthy signal to reappear within the "healthy window" timeout)
327
NoCS CB2ManClose
Indicates that the check synchronism signal has failed to appear for a manual close
328
CB2 AR Lockout
Indicates an auto-reclose lockout condition - no further auto-reclosures possible until resetting
329
AR CB2 Unhealthy
Auto-reclose circuit breaker unhealthy signal, output from auto-reclose logic. Indicates during auto-reclose in progress, if the circuit
breaker has to become healthy within the circuit breaker healthy time window
330
AR CB2 No C/S
Indicates during auto-reclose in progress, if system checks have not been satisfied within the check synchronizing time window
331
Invalid AR Mode
AR Mode selected via optos is not supported
333
InValid Mesg Fmt
Invalid Message Format
334
Main Prot. Fail
Indicates a failure in differential or distance or DEF
337
Comms Changed
This is an alarm which indicates that C3794 comms have been changed to standard or vice versa and relay must be rebooted
338
Max Prop. Alarm
Maximum Propagation Delay Alarm
339
Prot'n Disabled
Protection disabled
340
9-2 Sample Alarm
Means the abnormal state of IEC 61850-9-2LE sample
342
9-2LE Cfg Alarm
This DDB means the IEC 61850-9-2LE configure is wrong
344
SR User Alarm 1
Triggers user alarm 1 message to be alarmed on LCD display (self-resetting)
345
SR User Alarm 2
Triggers user alarm 2 message to be alarmed on LCD display (self-resetting)
346
SR User Alarm 3
Triggers user alarm 3 message to be alarmed on LCD display (self-resetting)
347
SR User Alarm 4
Triggers user alarm 4 message to be alarmed on LCD display (self-resetting)
348
MR User Alarm 5
Triggers user alarm 5 message to be alarmed on LCD display (manual-resetting)
349
MR User Alarm 6
Triggers user alarm 6 message to be alarmed on LCD display (manual-resetting)
350
MR User Alarm 7
Triggers user alarm 7 message to be alarmed on LCD display (manual-resetting)
351
MR User Alarm 8
Triggers user alarm 8 message to be alarmed on LCD display (manual-resetting)
352
Battery Fail
P446SV-TM-EN-1
SIGNAL NAME
DDB_BREAKER_FAIL_ALARM_2
DDB_CB2_MONITOR_ALARM
DDB_CB2_MONITOR_LOCKOUT
DDB_CB2_STATUS_ALARM
DDB_CB2_FAILED_TO_TRIP
DDB_CB2_FAILED_TO_CLOSE
DDB_CONTROL_CB2_UNHEALTHY
DDB_CONTROL_NO_CHECK_SYNC_2
DDB_AR_LOCKOUT_2
DDB_AR_CB2_UNHEALTHY
DDB_AR_NO_CHECK_SYNC_2
DDB_INVALID_AR_MODE
DDB_MESSAGE_FORMAT_FAIL
DDB_MAIN_PROTECTION_FAIL
DDB_PROT_COMMS_MODE
DDB_MAX_PROP_DELAY_ALARM
DDB_PROTECTION_DISABLED
DDB_ALARM_9_2_SAV
DDB_9_2_SAV_CFG_ALARM
DDB_ALARM_56
DDB_ALARM_57
DDB_ALARM_58
DDB_ALARM_59
DDB_ALARM_60
DDB_ALARM_61
DDB_ALARM_62
DDB_ALARM_63
DDB_BATTERY_FAIL
ELEMENT NAME
DESCRIPTION
Appendix B -Settings and Signals