P446SV
MENU TEXT
Displays the level of cyber security implemented, 1 = phase 1.
Password
Encrypted password entry cell. Not visbile via UI
Password Level 1
Allows user to change Encryped password level 1. Not visbile via UI
Password Level 2
Allows user to change Encryped password level 2. Not visbile via UI
Password Level 3
Allows user to change Encryped password level 3. Not visbile via UI
VIEW RECORDS
This column contains record configuration
Select Event
Setting range from 0 to 511. This selects the required event record from the possible 512 that may be stored. A value of 0 corresponds to the
latest event and so on.
Menu Cell Ref
Indicates the type of event. See Event sheet for more details
Time & Date
Time & Date Stamp for the event given by the internal Real Time Clock.
Event Text
Up to 32 Character description of the Event (refer to following sections).
Event Value
Up to 32 Bit Binary Flag or integer representative of the Event (refer to following sections).
Select Fault
Setting range from 0 to 14. This selects the required fault record from the possible 15 that may be stored. A value of 0 corresponds to the
latest fault and so on.
Faulted Phase
Displays the faulted phase. Started phases + tripped phases
Start Elements 1
P446SV-TM-EN-1
COL
ROW
DEFAULT SETTING
00
E1
00
E2
00
E3
00
E4
01
00
01
01
0
01
02
(From Record)
01
03
(From Record)
01
04
01
05
01
06
0
01
07
01
08
DESCRIPTION
second character of a pair
Each character is in the Courier range 33 - 122
[Integer]
4 registers for writing encrypted password
Registers can contain any bit pattern.
[ASCII Password (8)]
4 registers for writing encrypted password
Registers can contain any bit pattern.
[ASCII Password (8)]
4 registers for writing encrypted password
Registers can contain any bit pattern.
[ASCII Password (8)]
4 registers for writing encrypted password
Registers can contain any bit pattern.
[ASCII Password (8)]
From 0 to 499 in steps of 1
[Unsigned Integer (16 bits)]
Menu Cell Ref
[Cell Reference]
Time & Date
[IEC870 Time & Date]
Event Text
[ASCII Text (32)]
Event Value
[Binary Flag (32)/UINT32]
From 0 to 4 in steps of 1
[Unsigned Integer (16 bits)]
Start A
Start B
Start C
Start N
Trip A
Trip B
Trip C
Trip N
[Binary Flag (8)]
General Start
Start I Diff
Start Z1
Start Z2
Start Z3
Start ZP
Start Z4
Start I>1
Start I>2
Appendix B -Settings and Signals
AVAILABLE OPTIONS
B5