Appendix B -Settings and Signals
MENU TEXT
RP1 Protocol
Indicates the communications protocol that will be used on the rear communications port.
RP1 Address
Courier or IEC60870-5-103 versions only. This cell sets the unique address for the relay such that only one relay is accessed by master
station software.
RP1 Address
DNP3.0 versions only. This cell sets the unique address for the relay such that only one relay is accessed by master station software.
RP1 InactivTimer
This cell controls how long the relay will wait without receiving any messages on the rear port before it reverts to its default state, including
resetting any password access that was enabled.
RP1 Baud Rate
IEC60870-5-103 versions only. This cell controls the communication speed between relay and master station. It is important that both relay
and master station are set at the same speed setting.
RP1 Baud Rate
DNP3.0 versions only. This cell controls the communication speed between relay and master station. It is important that both relay and
master station are set at the same speed setting.
RP1 Parity
DNP3.0 versions only. This cell controls the parity format used in the data frames. It is important that both relay and master station are set
with the same parity setting.
RP1 Meas Period
IEC60870-5-103 versions only. This cell controls the time interval that the relay will use between sending measurement data to the master
station.
RP1 PhysicalLink
This cell defines whether an electrical EIA(RS) 485 or fiber optic connection is being used for communication between the master station and
relay. If 'Fiber Optic' is selected, the optional fiber optic communications board will be required.
RP1 Time Sync
DNP3.0 versions only. If set to Enabled the master station can be used to synchronize the time on the relay. If set to Disabled either the
internal free running clock or IRIG-B input are used.
RP1 CS103Blcking
IEC60870-5-103 versions only. There are three settings associated with this cell:
Disabled - No blocking selected.
Monitor Blocking - When the monitor blocking DDB Signal is active high, either by energizing an opto input or control input, reading of the
status information and disturbance records is not permitted. When in this mode the relay returns a "termination of general interrogation"
message to the master station.
Command Blocking - When the command blocking DDB signal is active high, either by energizing an opto input or control input, all remote
B46
COL
ROW
DEFAULT SETTING
0E
01
0E
02
255
0E
02
1
0E
03
15
0E
04
19200 bits/s
0E
04
19200 bits/s
0E
05
None
0E
06
10
0E
07
Copper
0E
08
Disabled
0E
0A
Disabled
DESCRIPTION
Courier
IEC870-5-103
Modbus
DNP 3.0
[Indexed String]
From 0 to 255 in steps of 1
[Unsigned Integer (16 bits)]
From 0 to 65519 in steps of 1
[Unsigned Integer (16 bits)]
From 1 to 30 in steps of 1
[Courier Number (time-minutes)]
9600 bits/s
19200 bits/s
[Indexed String]
1200 bits/s
2400 bits/s
4800 bits/s
9600 bits/s
19200 bits/s
38400 bits/s
[Indexed String]
Odd
Even
None
[Indexed String]
From 1 to 60 in steps of 1
[Courier Number (time-seconds)]
Copper
Fibre Optic
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Monitor Blocking
Command Blocking
[Indexed String]
AVAILABLE OPTIONS
P446SV-TM-EN-1
P446SV