Autoreclose Lockout - GE MiCOM P40 Technical Manual

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
5.19

AUTORECLOSE LOCKOUT

A number of events will cause Autoreclose lockout. If this happens an Autoreclose lockout alarm is raised. In this
condition, Autoreclose cannot be initiated until the corresponding lockout has been reset.
The following events force Autoreclose lockout:
Protection operation during reclaim time. Following the final Autoreclose attempt, if the protection operates
during the reclaim time, the AR cycle goes to AR lockout and the Autoreclose function is disabled until the
AR lockout condition is reset.
Persistent fault. A fault is considered persistent if the protection re-operates after the last permitted shot.
Block Autoreclose. If the block Autoreclose DDB is asserted whilst Autoreclose is in progress, the cycle goes
to lockout.
Protection function selection. Setting 'Block AR' against a particular protection function in the AUTORECLOSE
column means that operation of the protection will block Autoreclose and force lockout.
Circuit breaker failure to close. If a circuit breaker fails to close Autoreclose is blocked and forced to lockout.
Circuit breaker remains open at the end of the reclaim time. An Autoreclose lockout is forced if the circuit
breaker is open at the end of the reclaim time.
Circuit breaker fails to close when the close command is issued.
Circuit breaker fails to trip correctly.
Three-phase dead time started by 'line dead' violation. If the line does not go dead within the Dead Line
Time setting, the logic forces the Autoreclose sequence to lockout. Determination of when to start the timer
is made in the 3PDTStart WhenLD setting.
Block Follower if Leader fails to close is set. If the setting BF if Lfail Cls in the AUTORECLOSE column is set to
Enable, the active Follower circuit breaker will lockout if the Leader circuit breaker fails to reclose.
Leader/Follower invalid selection using opto-isolated input. If the Leader/Follower Autoreclose mode in the
AUTORECLOSE settings is set to be selected using the opto-isolated inputs, then if the logic detects an invalid
Autoreclose mode combination, it forces both circuit breakers to lockout if a trip occurs.
P446SV-TM-EN-1
Chapter 11 - Autoreclose
325