GE MiCOM P40 Technical Manual page 848

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

Appendix B -Settings and Signals
MENU TEXT
Z3 Gnd. Angle
Setting of line angle (positive sequence) for zone 3.
Z3' Gnd Rev Rch
Setting for Z3 offset (reverse) reach. This setting is only visible if 'Z3 Offset' is enabled in 'GROUP x DISTANCE SETUP'.
Z3 Dynamic Tilt
Setting that enables or disables Z3 top reactance line dynamic tilting. If set enabled, the top line angle will be automatically shifted by the
angle difference between the fault current and negative sequence current, starting from the 'Z3 Tilt top line' angle setting – see the next cell.
The ZP, as over-reaching zone, is allowed only to tilt up. If Dynamic tilting is disabled, the top line will be shifted by the 'ZP Tilt top line' setting
(Predetermined tilting by fixed angle).
This setting is visible only when ground characteristic is set to 'Quad' and Z3 offset disabled.
Z3 Tilt Top Line
Setting of the Z3 tilt angle. Minus angle tilts the reactance line downwards This setting is visible only when the above setting is visible.
kZN3 Res. Comp.
Setting of Z3 residual compensation magnitude.
kZN3 Res. Angle
Setting of Z3 residual compensation angle.
kZm3 Mut. Comp.
Setting of Z3 mutual compensation magnitude.
kZm3 Mut. Angle
Setting of Z3 mutual compensation angle.
R3 Gnd. Res. Fwd
Setting for Z3 resistive reach that defines Quad's right hand line.
R3' Gnd Res. Rev
Setting for Z3 resistive reach that defines Quad's left hand line. This is settable only if Ground Chars. is Quad and Z3 offset is enabled
otherwise is fixed to 25% of the right hand blinder.
Z3 Sensit Ignd>3
Zone 3 current sensitivity.
ZP Gnd. Reach
Setting for ZP reach.
ZP Gnd. Angle
Setting of line angle (positive sequence) for zone P.
ZP Dynamic Tilt
Setting that enables or disables ZP top reactance line dynamic tilting. If set enabled, the top line angle will be automatically shifted by the
angle difference between the fault current and negative sequence current, starting from the 'ZP Tilt top line' angle setting – see the next cell.
The ZP, as over-reaching zone, is allowed only to tilt up. If Dynamic tilting is disabled, the top line will be shifted by the 'ZP Tilt top line' setting
(Predetermined tilting by fixed angle).
This setting is visible only when ground characteristic is set to 'Quad'.
ZP Tilt Top Line
Setting of the ZP tilt angle. Minus angle tilts the reactance line downwards This setting is visible only when the above setting is visible.
kZNP Res. Comp.
Setting of ZP residual compensation magnitude.
kZNP Res. Angle
B102
COL
ROW
DEFAULT SETTING
32
71
70
32
72
1
32
73
Enabled
32
74
-3
32
75
1
32
76
0
32
77
1
32
78
0
32
79
25
32
7A
1
32
7C
0.05
32
80
20
32
81
70
32
83
Enabled
32
84
-3
32
85
1
32
86
0
DESCRIPTION
From 20 to 90 in steps of 1
[Courier Number (angle)]
From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1
[Courier Number (impedance)]
Disabled
Enabled
[Indexed String]
From -30 to 30 in steps of 1
[Courier Number (angle)]
From 0 to 10 in steps of 0.01
[Courier Number]
From -180 to 90 in steps of 0.1
[Courier Number (angle)]
From 0 to 10 in steps of 0.01
[Courier Number]
From -180 to 90 in steps of 0.1
[Courier Number (angle)]
From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1
[Courier Number (impedance)]
From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1
[Courier Number (impedance)]
From 0.05*I1 to 2*I1 in steps of 0.005*I1
[Courier Number (current)]
From 0.05*v1/I1 to 500*V1/I1 in steps of 0.01*V1/I1
[Courier Number (impedance)]
From 20 to 90 in steps of 1
[Courier Number (angle)]
Disabled
Enabled
[Indexed String]
From -30 to 30 in steps of 1
[Courier Number (angle)]
From 0 to 10 in steps of 0.01
[Courier Number]
From -180 to 90 in steps of 0.1
AVAILABLE OPTIONS