Trip On Close Schemes; Figure 107: Trip On Close Logic - GE MiCOM P40 Technical Manual

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
4

TRIP ON CLOSE SCHEMES

Logic is provided for situations where special tripping may be necessary following closure of the associated circuit
breaker. Two cases of Trip on Close (TOC) logic are catered for:
Switch on to Fault (SOTF).
Trip on Reclose (TOR)
SOTF provides instantaneous operation of selected elements if a fault is present when manual closure of the circuit
breaker is performed.
TOR provides instantaneous operation of selected elements if a persistent fault is present when the circuit breaker
attempts autoreclosure
The SOTF and TOR functions are known as Trip on Close logic. Both methods operate in parallel if mapped to the
SOTF and TOR Tripping matrix in the setting file.
The settings for Switch on to Fault (SOTF) and Trip on Reclose (TOR) are located in the TRIP ON CLOSE section of the
SCHEME LOGIC column.
SOTF and TOR are complemented by Current No Voltage level detectors (also known as CNV level detectors). These
CNV level detectors are set using the voltage and current settings located in the CB FAIL & P.DEAD column. The
same settings are used for pole dead logic detection. A 20ms time delay in the logic avoids a possible race
between very fast overvoltage and undercurrent level detectors.
The following figures show the Trip On Close function in relation to the Distance zones and the Trip On Close
function when driven by Current No Volt level detectors.
TOR Status
Enabled
Inhibit TOR
Any Pole Dead
TOC Delay
TOC Reset Delay
Inhibit SOTF
All Poles Dead
SOTF Delay
SOTF Pulse
SOTF Status
Enabled PoleDead
En Pdead + Pulse
Enabled ExtPulse
Set SOTF
V02742

Figure 107: Trip On Close logic

P446SV-TM-EN-1
485
891
486
890
&
1
1
&
488
Chapter 9 - Non-Aided Schemes
S
Q
R
&
S
Q
R
878
&
TOR Active
877
TOC Active
1
879
SOTF Active
217