GE MiCOM P40 Technical Manual page 833

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
MENU TEXT
X.21, or generally 56kbit/s for V.35.
For direct fiber connection between relays, 64kbit/s will offer slightly faster data transmission.
The setting is invisible when IEEE C37.94 Comm Mode is selected.
Baud Rate Ch2
Channel 2 data rate setting for signalling between ends. The setting will depend on the MUX electrical interface, set 64kbit/s for G.703 and
X.21, or generally 56kbit/s for V.35.
For direct fiber connection between relays, 64kbit/s will offer slightly faster data transmission.
The setting is invisible when IEEE C37.94 Comm Mode is selected.
Clock Source Ch1
Setting that defines which clock source is used to synchronize data transmissions over channel 1. The setting will depend on
communications configuration and external clock source availability. If relays are connected direct fiber over channel 1, 'Internal' setting
should be selected. If channel 1 is routed via a multiplexer, either setting may be required (see Application Notes).
Clock Source Ch2
Setting that matches the clock source being used for data synchronization over channel 2.
Ch1 N*64kbits/s
Setting for channel 1 when connected to MUX. When set to 'Auto' P54x will configure itself to match the multiplexer.
The setting is visible only when IEEE C37.94 Comm Mode is selected.
Ch2 N*64kbits/s
Setting for channel 2 when connected to Mux.
The setting is visible only when IEEE C37.94 Comm Mode is selected.
Comm Fail Timer
Time delay after which the 'Channel Fail Alarm' will be issued providing that no messages were received during the 'Channel Timeout' period
or the 'Alarm Level' is exceeded.
Comm Fail Mode
Fail mode setting that triggers the 'Channel Fail Alarm', providing that the Dual Redundancy or 3 ended scheme is set.
P446SV-TM-EN-1
COL
ROW
DEFAULT SETTING
20
12
64kbits/s
20
13
Internal
20
14
Internal
20
15
1
20
16
1
20
18
10
20
19
Ch 1 or 2 Fail
DESCRIPTION
64kbits/s
56kbits/s
[Indexed String]
Internal
External
[Indexed String]
Internal
External
[Indexed String]
Auto
1
2
3
4
5
6
7
8
9
10
11
12
[Indexed String]
Auto
1
2
3
4
5
6
7
8
9
10
11
12
[Indexed String]
From 0.1 to 600 in steps of 0.1
[Courier Number (time-seconds)]
Ch 1 Failure
Ch 2 Failure
Ch 1 or 2 Fail
Ch 1 and 2 Fail
[Indexed String]
Appendix B -Settings and Signals
AVAILABLE OPTIONS
B87

Advertisement

Table of Contents
loading