P446SV
CB2 I^ Maint
Alarm Enabled
Greatest broken current total
CB2 I^ Maint
CB2 I^ Lockout
Alarm Enabled
CB2 I^ Lockout
No.CB2 Ops Maint
Alarm Enabled
Max no . of CB operations
No.CB2 Ops Maint
No.CB2 Ops Lock
Alarm Enabled
No.CB2 Ops Lock
CB2FltFreqLock
Alarm Enabled
Fault frequency count
CB2FltFreqCount
CB2 Time Maint
Alarm Enabled
Greatest CB operate time
CB2 Time Maint
CB2 Time Lockout
Alarm Enabled
CB2 Time Lockout
Clear Alarms
Reset CB2 Data
Yes
Rst CB2 Data
Reset CB2 Lockout Alarm
Control CB2 Unhealthy
CB2 Control no Check Synch
CB2 failed to trip
CB2 failed to close

Figure 232: CB2 Condition Monitoring logic diagram

5.7

RESET CIRCUIT BREAKER LOCKOUT

Lockout conditions caused by the circuit breaker condition monitoring functions can be reset according to the
condition of the Rst CB mon LO by setting found in the CB CONTROL column. There are two options; CB Close
and User interface.
If set to CB Close, a timer setting, CB mon LO RstDly, becomes visible. When the circuit breaker closes, the CB
mon LO RstDly time starts. The lockout is reset when the timer expires.
If set to User Interface then a command, CB mon LO reset, becomes visible. This command can be used to
reset the lockout from a user interface.
An Autoreclose lockout generates an Autoreclose lockout alarm. Autoreclose lockout conditions can be reset by
various commands and setting options found under the CB CONTROL column.
P446SV-TM-EN-1
&
&
&
&
&
-1
&
&
-1
&
&
1
Chapter 16 - Monitoring and Control
&
S
Q
1
R
&
S
Q
R
1
S
Q
R
1
&
S
Q
R
1
S
Q
R
CB2 I^ Maint
CB2 Monitor Alm
CB2 I^ Lockout
No.CB2 Ops Maint
No.CB2 Ops Lock
CB2 Pre-Lockout
CB2FaultFreqLock
CB2 Mon LO Alarm
CB2 Time Maint
CB2 Time Lockout
CB2 LO Alarm
V01284