Resistor Values; Psl For Tcs Scheme 3; Figure 253: Psl For Tcs Scheme 3 - GE MiCOM P40 Technical Manual

P446sv
Hide thumbs Also See for MiCOM P40:
Table of Contents

Advertisement

P446SV
supervision current is maintained through the trip path with the breaker in either state, therefore providing pre-
closing supervision.
4.3.1

RESISTOR VALUES

Resistors R1 and R2 are used to prevent false tripping, if the opto-input is accidentally shorted. However, unlike the
other two schemes. This scheme is dependent upon the position and value of these resistors. Removing them
would result in incomplete trip circuit monitoring. The table below shows the resistor values and voltage settings
required for satisfactory operation.
Trip Circuit Voltage
48/54
110/250
220/250
Warning:
This Scheme is not compatible with Trip Circuit voltages of less than 48 V.
4.3.2

PSL FOR TCS SCHEME 3

Opto Input
*NC stands for Normally Closed.

Figure 253: PSL for TCS Scheme 3

P446SV-TM-EN-1
Opto Voltage Setting with R1
Fitted
24/27
48/54
110/125
0
dropoff
400
&
Resistor R1 & R2 (ohms)
1.2k
2.7k
5.0k
50
pickup
0
Chapter 17 - Supervision
Resistor R3 (ohms)
600
1.2k
2.5k
0
*Output Relay
Straight
0
Latching
LED
User Alarm
V01217